Hardware overview

The storage system consists of a controller chassis and one or more drive chassis mounted in a 19-inch rack.

Controller chassis

The controller chassis contains the following components:

  • Controller boards (CTLs, also called DKCs.)
  • Front-end modules (FEMs), also called channel boards (CHBs)
  • Back-end modules (BEMs), also called disk boards (DKBs)
  • Power supply (PS)
  • Backup fan module (BKMF)
  • Accelerator FAN Module (ACFL)

The CTLs contain the cache memory (CM) and cache flash memory (CFM) for the storage system. The VSP E1090 supports 1,024 GiB of cache memory.

GUID-E773272D-B328-4341-BBEB-7DB7BB674886-low.png
Number Item Description
1 LED (POWER, READY, WARNING, ALARM)Status LEDs for the controller chassis.
2 POWER ON/OFF (main switch)

Switch that controls power to the storage system.

3 Lock Use to lock and unlock front bezel.
GUID-C473DEC4-1E49-4EA5-A4DF-71E9F21B087F-low.png
Number Item Description
1 POWER LED Green: Storage system is powered on.

Amber: Storage system is receiving power.

2 READY LED Green: Normal operation.
3 WARNING LED Off: Normal operation.

Amber: Component requires maintenance.

Blink: Failure requires maintenance.

Note: When system option mode (SOM) 1097 is set to ON, the WARNING LED does not blink, even if the following failure service information messages (SIMs) are issued: 452xxx, 462xxx, 3077xx, 4100xx, and 410100.

LED might turn off during user maintenance.

4 ALARM LED Off: Normal operation.

Red: Processor failure (system might be down). For assistance, contact customer support: https://support.hitachivantara.com/en_us/contact-us.html.

GUID-0D62DA7D-0B28-4A21-B22C-14CFD7E37ABB-low.png

Number Item Description
1 ControllersController 1 (bottom) and Controller 2 (top).
2Backup module N/A
3 BACKUP LED Green: Power restoration in progress following power outage.

Fast blink green: Restoring.

Slow blink green: Restoring, or sequential shutdown in progress.

4Cache flash memoryN/A
5ALM LED (for cache flash memory)Red: Cache flash memory can be removed.
6CTL ALM LED Red: Controller can be removed.

Blink red: Failure with the power supply unit of the controller.

Amber: LAN reset switch was pressed.

7LAN-RST switch Use only when instructed by customer support.
8STATUS LED (for BKMF) Green: Charging of the battery in the backup module is complete.

Red: Backup module can be removed.

Blink red one time: Main battery failure.

Blink red two times: Backup battery failure.

Blink red three times: Both batteries failed or preventive maintenance replacement of batteries can run.

Off: Battery is not mounted, battery-mounting failure occurred, or firmware is being upgraded. Off is normal status for configurations without batteries.

9POWER ON/OFF (main switch) Powers the storage system.
10POWER, READY, WARNING, and ALARM LEDs Note: When system option mode (SOM) 1097 is set to ON, the WARNING LED does not blink, even if the following failure service information messages (SIMs) are issued: 452xxx, 462xxx, 3077xx, 4100xx, and 410100.

GUID-11728786-98E8-4003-A3BA-B3BAF903D100-low.png

Number Item
1 Power supply
2Disk board module
3 LAN board
4Channel board module
GUID-BFCDF0DF-5CE1-4382-8964-B03F690BA79C-low.png
Number Item Description
1 ALM / RDY LED Red: Power supply unit can be replaced.
2RDY LED Green: Normal operation.

Controller board

GUID-7D835195-EA39-4366-8592-A0819B24C599-low.png
Number ItemDescription
1 STATUS LED Off: Battery is uninstalled, installed improperly or BKMF firmware is replaced (in case of a configuration with no battery installed, the LEDs for BKMF-10 and BKMF-20 go out).

Green On: Battery is fully charged.

Green Blinking: Battery is charged or discharged.

Red On: BKMF has an error.

Red Blinking: BKMF can be removed. A failure occurred in the battery or preventive maintenance replacement of the batteries is possible.

2 LAN-RST This is a switch for GUM reset.

If GUM reboot fails, reset GUM forcibly from the hardware.

3CTL ALM Red On: The controller board is ready to be removed (when the maintenance work requiring insertion and removal of the controller board is performed). A failure is detected in the controller board (when the maintenance work mentioned above is not performed).

Red Blinking: A failure is detected in the controller board, cache memory, or cache flash memory (CFM).

Amber On: Indicates that the LAN RESET switch is pressed.
4BACKUP STS Green On : Indicates that power outage has occurred or power restoration is in progress after power outage.
  • Fast blinking (On and off are repeated at 0.1-second intervals.): The data is being restored.
  • Slow blinking (On and off are repeated at 0.5-second intervals.): A planned power off is being executed or the data is being stored.
5ALARM Red On: Cache Flash Memories are removable.
GUID-0D0CE03D-3A6E-4F57-A398-D54B2DA0DCD7-low.png
Number Item Description
1 ACT/LINK LEDAmber: Link status/data transfer status.
2SPEED LEDOn: Link speed = 1 Gbps.

Off: Link speed = 10 Mbps/100 Mbps.

3 LAN ALARM LEDRed: The removal of the LAN Board is possible.

Front-end modules

The front-end modules (FEMs), also called channel boards (CHBs), control the transfer of data between the host and cache memory. The storage system supports Fibre Channel (FC) and iSCSI front-end modules (FEMs) for attachment to host servers. The front-end module LEDs indicate the operating status of the module.

Front-end module specifications
SpecificationFibre 32-Gbps ReadyiSCSI 10GiSCSI 10G BASE-T
Model numberDKC-F910I-4HF32RDKC-F910I-2HS10SDKC-F910I-2HS10B
Number of PCBs111
Host interfaceFCPiSCSI (optical)iSCSI (copper)
Data transfer rate (MB/s)16Gbps: 400/800/1,600

32Gbps: 800/1,600/3,200

1,000100/1,000
Number of options installed( ): DKB slot used2/4/6/8/12/14/16 (14/16/18/20)2/4/6/8/12/14/16 (14/16/18/20)2/4/6/8/12/14/16 (14/16/18/20)
Number of ports per PCB422
Number of ports per storage system( ): DKB slot used8/16/24/32/48/56/64 (56/64/72/80)4/8/12/16/24/28/32 (28/32/36/40)4/8/12/16/24/28/32 (28/32/36/40)
Maximum cable lengthShort wave1400m/190m/125m/100m550m-
Long wave10km--
Copper--50m (cat 6a)
  1. When 50/125mm laser optimized multi-mode fibre cable (OM3 or OM4) is used. When using other cable types, contact customer support.

10-Gbps iSCSI board LEDs and connectors (optical)

GUID-DB08A169-9D7F-4EF4-8FFA-2D626520C8BF-low.png
Number Item Description
1 STATUS LED Green: Front-end module is in the power-on state.

Red: Front-end module can be removed safely.

2 PORT LED Red: Small-form factor (SFF) pluggable can be removed.

Blue: Normal link status.

Blue Blinking: Front-end module is in communication status.

3 iSCSI connectors Connect to Ethernet cables.

10-Gbps iSCSI board LEDs and connectors (copper)

GUID-DB0656BF-12BC-47AF-9543-936FB46338DB-low.jpg
Number Item Description
1 STATUS LED Green: Front-end module is in the power-on state.

Red: Front-end module can be removed safely.

2 PORT (Link/Speed) LED Yellow: 1-Gbps link.

Green: 10-Gbps link.

Off: No link connection.

3 PORT LED Green: Link connection is established.

Blinking: Communication is in progress.

Off: No link connection or not ready to communicate.

4 iSCSI connectors Connect to Ethernet cables.

16-Gbps or 32-Gbps Fibre Channel (4-port) board LEDs and connectors

GUID-911F14BB-9878-4122-B881-AE44058B572A-low.png
Number Item Description
1 Fibre Channel connectors Connect to Fibre Channel cables.
2 STATUS LED Green: Front-end module is in power-on state.

Red: Front-end module can be removed safely.

3 PORT LED Red: Small-form factor (SFF) pluggable can be removed.

Blue: Normal link status at 16 Gbps (16 Gbps).

Blue: Normal link status at 32 Gbps (32 Gbps).

Green: Normal link status at 4 Gbps or 8 Gbps (16 Gbps).

Green: Normal link status at 8 Gbps or 16 Gbps (32 Gbps).

The following table lists the Fibre Channel port assignments

Port assignments
CHB number 16-Gbps, or 32-Gbps Fibre Channel ports (left to right)
Port 1 Port 2 Port 3 Port 4
CHB-1A 1A 3A 5A 7A
CHB-1B 1B 3B 5B 7B
CHB-1C 1C 3C 5C 7C
CHB-1D 1D 3D 5D 7D
CHB-1E 1E 3E 5E 7E
CHB-1F 1F 3F 5F 7F
CHB-1G 1G 3G 5G 7G
CHB-1H 1H 3H 5H 7H
CHB-2A 2A 4A 6A 8A
CHB-2B 2B 4B 6B 8B
CHB-2C 2C 4C 6C 8C
CHB-2D 2D 4D 6D 8D
CHB-2E 2E 4E 6E 8E
CHB-2F 2F 4F 6F 8F
CHB-2G 2G 4G 6G 8G
CHB-2H 2H 4H 6H 8H

Back-end modules

The back-end modules (BEMs), also called disk boards (DKBs), control the transfer of data between the drives and cache memory. The back-end module LEDs indicate the operating status of the module.

Back-end module specifications
ItemSpecification
Model numberDKC-F910I-BN8G
Number of PCBs1
Number of ports per PCB4
Performance 8 Gbps
Data encryption Not supported
Number of PCBs per storage system4 or 8
Number of NVMe ports per system8 or 16
GUID-E30C9EE2-2227-4517-A70A-C6D8714EF29F-low.png
Number Item Description
1 STATUS LED Green: Back-end module is in the power-on state.

Red: Back-end module can be removed safely.

2 PORT LED Blue: Link status is normal.
3 PATH 0 connector Connect to a drive tray.
4 PATH 1 connector Connects to a drive tray.

LAN blade LEDs and connectors

LAN blade
Number Item Description
1 LINK LED Green: Link status is normal.
2 ACT LED Orange: Data is being transferred.
3 LAN 2 LAN port used by the user.
4 LAN 1 Maintenance LAN port used by service personnel.
5 LAN ALARM LED Red: LAN blade can be removed.
6 Uninterruptible power supply (UPS) port N/A

PCIe module

GUID-82FCDA07-BB45-441E-AEBE-D27F5B946933-low.jpg
Number Item Description
1 STATUS LED Green: PCIe module is in the power-ON status.

Red: PCIe module failure occurred.

Off: PCIe module can be removed safely.

2 Link Green: PCIe is Gen-3 (8-Gbps) and is linked up normally.

Off: PCIe is not linked up (PCIe cable might not be connected). If a PCIe cable is connected, it can be removed safely.

NVMe drive tray (DBN)

The following table describes the physical specifications of the NVMe drive tray.

NVMe drive tray specifications

Name

Model name

Height

Number of drive slots

Drive type

DBN

DW-F850-DBN

2U (88.2 mm)

24

2.5 inch

DBNE

DW-F1000-DBNE

2U (88.2 mm)

24

2.5 inch

NVMe display LEDs

GUID-CEF56240-66F9-4FC4-831B-CE6641E4F39E-low.png
Number Item Description
1ALMRed: Indicates that the removal of the HDD/SSD is possible when the storage system is powered on.
2ACTGreen: Indicates that the drives are powered on.

Blinking Green: Indicates that the drives are active.

3 POWERGreen: Indicates that power is supplied to the ENC.
4 READYGreen: Indicates that the ENC is operating normally.
5 LOCATEAmber: An LED to specify the chassis location on the rear of the chassis.

The LED can be lit/turned off by Maintenance Utility.

NVMe rear panel

GUID-3E83FA9B-6629-4B7B-9D5C-449F5F70CBDB-low.png
Number Item Description
1 POWERGreen: Indicates that power is supplied to the ENC.
2 LOCATEAmber: An LED to specify the chassis location on the rear of the chassis.

The LED can be lit/turned off by Maintenance Utility.

3 ALARMRed: Indicates that the removal of the drive is possible when the storage system is powered on.
4 LINKBlue: Indicates that PCIe between DKBN and ENC is linked up.

NVMe AC power supply LED

GUID-08DF12AD-F4E4-46CF-A76E-B9F32E7E16FB-low.png
Number Item Description
1 RDY2Green: Normal operation

Off: Erroneous operation or out of operation

2 RDY1Green: Normal operation

Off: Erroneous operation or out of operation

3 AC IN Green: Indicates that AC input is normal.
4 ALM (REPLACE) Red: Indicates when the power supply can be replaced.

Small-form-factor drive tray (DBS)

The following table describes the physical specifications of the small-form-factor drive tray.

DBS drive tray specifications

Name

Model name

Height

Number of drive slots

Drive type

DBS

DW-F1000-DBS

2U (88.2 mm)

24

2.5 inch (SFF)

DBSE

DW-F1000-DBSE

2U (88.2 mm)

24

2.5 inch (SFF)

SFF front panel with bezel

GUID-13637890-D10D-4AB5-8C2B-DC603000A876-low.png
Number Item Description
1 POWER LED

Green: Drive tray is powered on.

2 READY LED

Green: Drive tray is operational.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 Lock

Locks and unlocks the front panel bezel by using the supplied key.

SFF front panel without bezel

GUID-F55EA696-0DF6-4FD7-B15D-E94A44E8825F-low.png
Number Item Description
1

POWER, READY, and LOCATE LEDs

Green: Drive tray is powered on.

Green: Drive tray is operational.

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
2

ALM LED

Red: Drive stopped due to a failure and can be replaced.
3

ACT LED

Green: Normal operation.

Blink green: Drive is being accessed.

4 Small-form-factor drives

The twenty-four 2.5-inch SFF drives are positioned vertically. The slots are organized from 0 to 23.

SFF rear panel

GUID-5448356A-2569-4EDE-AB09-CF1B321B7A84-low.png
Number Item Description
1 ENC N/A
2 POWER LED

Green: ENC is in the power-on state.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 ALARM LED

Red: ENC can be replaced.

5 PATH (IN) LED

Blue: IN side port is linked up.

6 PATH (IN) connector

Connects to a controller or drive tray.

7 PATH (OUT) LED

Blue: OUT side port is linked up.

8 PATH (OUT) connector

Connects to a drive tray.

9 Console

This port is reserved.

10 Power supply unit N/A
11 Receptacle

Connects to the power cable provided with the storage system.

12 AC IN LED

Green: Normal operation.

13 ALM LED

Red: Power supply unit can be replaced.

14 RDY LED

Green: Normal operation.

AC power supply unit LEDs and connectors

Both SFF and LFF drive trays are equipped with AC power supply units. The AC power supply units include LEDs to display their operating status.

NoteThe DBSE and DBLE power supplies have a Platinum efficiency rating.
GUID-8E5D5BDD-0E7C-49A4-9683-6F55A86B8BE1-low.jpg
Number Item Description
1 RDY LED

Green: Normal operation.

2 ACI IN LED

Green: AC input is operating normally.

3 ALM LED

Red: Power supply unit can be replaced.

Small-form-factor drive tray (DBS2)

The following table describes the physical specifications of the small-form-factor drive tray.

DBS2 drive tray specifications

Name

Model name

Height

Number of drive slots

Drive type

DBS2

DW-F1000-DBS2

2U (88.2 mm)

24

2.5 inch (SFF)

DBS2E

DW-F1000-DBS2E

2U (88.2 mm)

24

2.5 inch (SFF)

SFF front panel with bezel

GUID-13637890-D10D-4AB5-8C2B-DC603000A876-low.png
Number Item Description
1 POWER LED

Green: Drive tray is powered on.

2 READY LED

Green: Drive tray is operational.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 Lock

Locks and unlocks the front panel bezel by using the supplied key.

SFF front panel without bezel

GUID-F55EA696-0DF6-4FD7-B15D-E94A44E8825F-low.png
Number Item Description
1

POWER, READY, and LOCATE LEDs

Green: Drive tray is powered on.

Green: Drive tray is operational.

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
2

ALM LED

Red: Drive stopped due to a failure and can be replaced.
3

ACT LED

Green: Normal operation.

Blink green: Drive is being accessed.

4 Small-form-factor drives

The twenty-four 2.5-inch SFF drives are positioned vertically. The slots are organized from 0 to 23.

SFF rear panel

GUID-B79860C5-619E-4035-A8A0-814E5A886D81-low.png
Number Item Description
1 PATH (IN) connector

Connects to a controller or drive tray.

2 PATH (OUT) connector

Connects to a drive tray.

3 ENCN/A
4 PATH (IN) LED

Blue: IN side port is linked up.

5 PATH (OUT) LED

Blue: OUT side port is linked up.

6 Console

These ports are reserved.

7 POWER LED

Green: ENC is in the power-on state.

8 LOCATE LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
9 ALARM LED Red: ENC can be replaced.
10 Power supply unitN/A
11 Receptacle

Connects to the power cable provided with the storage system.

12 ALM LED

Red: Power supply unit can be replaced.

13 AC IN LED

Green: Normal operation.

14 RDY1 LED

Green: Normal operation.

15 RDY2 LED

Green: Normal operation.

AC power supply unit LEDs and connectors

SFF drive trays are equipped with AC power supply units. The AC power supply units include LEDs to display their operating status.

GUID-B2F443F2-3744-4349-82A5-261135E40F8B-low.png
Number Item Description
1 RDY2 LED

Green: Normal operation.

2 RDY1 LED

Green: Normal operation.

3 Receptacle

Connects to the power cable provided with the storage system.

4 AC IN LED

Green: Normal operation.

5 ALM LED

Red: Power supply unit can be replaced.

Large-form-factor drive tray (DBL)

The following table describes the physical specifications of the large-form-factor (LFF) drive tray.

DBL drive tray specifications

Name

Model name

Height

Number of drive slots

Drive type

DBL

DW-F1000-DBL

2U (88.2 mm)

12

3.5 inch (LFF)

DBLE

DW-F1000-DBLE

2U (88.2 mm)

12

3.5 inch (LFF)

LFF front panel with bezel

GUID-13637890-D10D-4AB5-8C2B-DC603000A876-low.png
Number Item Description
1 POWER LED

Green: Drive tray is powered on.

2 READY LED

Green: Drive tray is operational.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 Lock

Locks and unlocks the front panel bezel by using the supplied key.

LFF front panel without bezel

GUID-4BECF9A6-B83F-44D2-B27D-2A03D733590F-low.png
Number Item Description
1

POWER, READY, and LOCATE LEDs

Green: Drive tray is powered on.

Green: Drive tray is operational.

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
2 ACT LED

Green: Normal operation.

Blink green: Drive is being accessed.

3

ALM LED

Red: Drive stopped due to a failure and can be replaced.
4 Large-form-factor drives

The twelve 3.5-inch LFF drives are positioned horizontally. The slots are organized in the following order:

8   9   10  11
4   5   6   7
0   1   2   3

LFF rear panel

GUID-5448356A-2569-4EDE-AB09-CF1B321B7A84-low.png
Number Item Description
1 ENC N/A
2 POWER LED

Green: ENC is in the power-on state.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 ALARM LED

Red: ENC can be replaced.

5 PATH (IN) LED

Blue: IN side port is linked up.

6 PATH (IN) connector

Connects to a controller or drive tray.

7 PATH (OUT) LED

Blue: OUT side port is linked up.

8 PATH (OUT) connector

Connects to a drive tray.

9 Console

This port is reserved.

10 Power supply unit N/A
11 Receptacle

Connects to the power cable provided with the storage system.

12 AC IN LED

Green: Normal operation.

13 ALM LED

Red: Power supply unit can be replaced.

14 RDY LED

Green: Normal operation.

AC power supply unit LEDs and connectors

Both SFF and LFF drive trays are equipped with AC power supply units. The AC power supply units include LEDs to display their operating status.

NoteThe DBSE and DBLE power supplies have a Platinum efficiency rating.
GUID-8E5D5BDD-0E7C-49A4-9683-6F55A86B8BE1-low.jpg
Number Item Description
1 RDY LED

Green: Normal operation.

2 ACI IN LED

Green: AC input is operating normally.

3 ALM LED

Red: Power supply unit can be replaced.

High-density intermix drive tray (DB60)

The following table describes the physical specifications of the high-density drive tray.

DB60 drive tray specifications

Name

Model name

Height

Number of drive slots

Drive type

DB60

DW-F1000-DB60

4U (176 mm)

60

3.5 inch (LFF)

DB60E

DW-F1000-DB60E

4U (176 mm)

60

3.5 inch (LFF)

Dense intermix drive tray front panel with bezel

GUID-3F46B854-0EB2-4764-82E5-D13B6CDB909F-low.png
Number Item Description
1 POWER LED

Green: Drive tray is powered on.

2 READY LED

Green: Drive tray is operational.

3 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
4 Lock

Locks and unlocks the front panel bezel by using the supplied key.

Dense intermix drive tray display LEDs

GUID-13ABD376-3D34-4719-83BE-B214368761DF-low.png
Number Item Description
1

ACT

Green: Normal operation.

Blink: Drive is being accessed.

2 ALM LED

Red: Drive stopped due to a failure and can be replaced.

NoteAt the rear of the drive tray, the drives are organized from left to right. On the left side of the preceding figure, the rear of the drive tray is at the top.
  • Rear of drive tray: 48-59
  • 36-47
  • 24-35
  • 12-23
  • Front of drive tray: 00-11

Dense intermix drive tray rear panel

GUID-1E2E8D8E-D303-4CA0-B35F-1D2FA19EBB0F-low.png
Number Item Description
1 Power supply unit N/A
2 RDY LED

Green: Normal operation.

3 AC IN LED

Green: Normal operation.

4 ALM LED

Red: Power supply unit can be replaced.

5 Receptacle

Connects to the power cable provided with the storage system.

6 ENC N/A
7 PATH (OUT) LED

Blue: OUT side port is linked up.

8 PATH (OUT) connector

Connects to a drive tray.

9 PATH (IN) LED

Blue: IN side port is linked up.

10 PATH (IN) connector

Connects to a controller or drive tray.

11 Console This port is reserved.
12 ALARM LED

Red: ENC can be replaced.

13 Locate LED

Amber:

  • Indicates the location of the chassis.
  • Can be turned on or turned off by the maintenance utility.
14 POWER LED

Green: ENC is in the power-on state.

Host port expansion chassis

The host port expansion chassis contains various interconnect adapters that connect a host system to storage and other network devices. The interconnect adapters include PCIe boards and iSCSI and FC cards.

Host port expansion chassis front-panel bezel LEDs

GUID-B8274511-A9D8-435A-B0D0-EEE306DBD776-low.jpg

Number Item Description
1 POWER LED Green: Host port expansion is turned on.

Amber: PCIe module is turned on.

Off: PCIe module is turned off.

2 Safety lock Lock or unlock the front bezel.

PCIe switchboard

GUID-7E7FE0DC-81D3-4440-B35F-A4ABF0F284B0-low.jpg

Number Item Description
1 STATUS LED Green: PCIe switchboard is powered on.

Red: PCIe switchboard can be replaced safely.

Off: PCIe switchboard is powered off.

Host port expansion chassis fan

GUID-B0CD88B6-C1A3-42B5-AA47-A039E0A852C0-low.jpg

Number Item Description
1 ALM LED Red: Fan failure has occurred.

Off: Normal operation.

PCIe cable connector

GUID-0D3D147E-D01D-4D24-A78F-C86972DC4B53-low.jpg

Number Item Description
1 STATUS LED Green: PCIe cable connector is powered on.

Red: PCIe cable connector can be replaced safely.

Off: PCIe cable connector is powered off.

2 Link Basic LED Green: Basic PCIe Gen-3.0 (8-Gbps) is linked up normally.

Off: Basic PCIe is not linked up (PCIe cable might not be connected). If a cable is connected, it can be removed safely.

3 InAct Basic LED Amber: Basic PCIe status changed from link up to link down and cables. Cables can be removed safely.

Off: Basic PCIe is normal or not set.

4 Link Option LED Green: Option PCIe Gen-3.0 (8-Gbps) is linked up normally.

Off: Option PCIe is not linked up (PCIe cable might not be connected). If a cable is connected, it can be removed safely.

5 InAct Option LED Amber: Option PCIe status changed from link up to link down and cables. Cables can be removed safely.

Off: Option PCIe is normal or not set.

Host port expansion chassis power supply

GUID-499921CC-4F44-48F2-B395-A3F0914FF576-low.jpg

Number Item Description
1 ALM / RDY LED Red: Host port expansion chassis power supply can be replaced safely.

Green: Normal operation.

2 AC IN LED Blue: AC input is normal.

Rack support

The storage system can be installed in the Hitachi Universal V3 Rack, Universal V2B Rack, or Universal V2 Rack as well as non-Hitachi 19-inch racks that meet the storage system's specifications.

Non-Hitachi racks must be 4-post, EIA 310-D compliant with adequate airflow and weight capacity. The PDUs must be mounted properly to avoid any issues for servicing the storage system. The PDU receptacles must face toward the back (not toward each other). The area behind the storage system and between the vertical 19-inch mounting posts must be free of PDUs and cable loops.