Specifications
The Hitachi Virtual Storage Platform E1090 (VSP E1090) storage system is designed to operate in a controlled environment such as a data center. The following tables provide the environmental, electrical, and physical requirements and specifications for the VSP E1090.
Environmental specifications
The following tables provide the environmental specifications, including operating and non-operating values, for the Hitachi Virtual Storage Platform E1090 (VSP E1090) storage system.
State | Specification | ||
Operating | 10°C to 35°C (50°F to 95°F) | ||
Non-operating | -10°C to 50°C (14°F to 122°F) | ||
Transport, storage | -30°C to 60°C (-22°F to 140°F) | ||
Temperature change rate | 10°C/hr (18°F/hr) |
State | Specification |
Operating | 8% to 80% |
Non-operating | 8% to 90% |
Transport, storage | 8% to 90% |
Maximum wet bulb temperature | 29°C (84.2°F) (noncondensing) |
Type | State | Specifications |
Vibration | Operating | 0.98 m/s2 (0.1 G) or less [frequency component 5 Hz to 100 Hz] |
Non-operating | Same as operating specification | |
Impact | Operating | No impact |
Non-operating | 78.4 m/s2 (8.0 G), 15 ms | |
Seismic wave | Operating | 2.5 m/s2 (0.25 G) (approximately 250 Gal) or less |
Non-operating | 3.9 m/s2 (0.4 G) or less: No critical damage for product function (normal operating with part replacement). 9.8 m/s2 (1.0 G) or less: Ensure own safety with fall prevention. |
State | Specification |
Operating | 3,050 m (10°C to 28°C) [10,006 ft. (50°F to 82.4°F)] 950 m (10°C to 35°C) [3,116 ft. (50°F to 95°F)] |
Non-operating | -60 m to 12,000 m (-196 ft. to 39,370 ft.) |
Type | State | Specifications |
Dust | Operating | 0.15 µg/m3 or less |
Non-operating | - | |
Gaseous contaminants | Operating | Within ANSI/ISA S71.04-2013 G1 classification levels. Keep data center clean by monitoring and controlling gaseous contamination. |
Non-operating |
State | Specification | ||
Operating | 90 dB or lower* | ||
Non-operating | 90 dB or lower* | ||
* Fire suppression systems and
acoustic noise: When activated, some inert-gas fire-suppression systems
release pressurized gas at high velocity through multiple nozzles in the data
center, generating high levels of acoustic noise. Pneumatic sirens can also generate
high levels of acoustic noise. High levels of acoustic noise can cause vibrations to
the media in the storage system, resulting in I/O errors, performance degradation in
the media, and to some extent damage to the drives. Media noise-level tolerance
varies among different models, designs, capacities, and manufacturers. The recommended acoustic noise level of 90 dB or less represents the current operating environment guidelines for which the storage systems are designed and manufactured for reliable operation when placed 2 meters or more from the source of the noise. NoteThe storage
systems and media are not tested for compatibility with fire-suppression systems
or pneumatic sirens. In addition, Hitachi does not recommend or claim
compatibility with any fire-suppression systems or pneumatic sirens. The
customer is responsible for following applicable regulations. To prevent I/O errors and damage to the storage system due to high levels of acoustic noise:
DAMAGE TO MEDIA FROM FIRE-SUPPRESSION SYSTEMS OR PNEUMATIC SIRENS VOIDS THE MEDIA WARRANTY. |
Electrical specifications
The VSP E1090 runs on single-phase AC power. The AC power input power for the storage systems is duplexed across the PDUs, enabling the equipment installed in the rack to remain powered on if power is removed from one of the two power distribution panels.
The following tables provide the electrical specifications for the VSP E1090 storage system, including input power and input voltage and frequency requirements.
Item | Component | Specification |
Rated power | Controller | 1,600 VA |
Drive tray | 800 VA | |
Input power1 | Controller | Single-phase AC 50 Hz/60 Hz 200 V to 240 V |
Drive tray | ||
Input current1,2 | Controller |
8.0 A |
Drive tray | 4.0 A | |
Steady current3 | Controller |
4.0 A |
Drive tray | 2.0 A | |
Leakage current | Controller | 1.75 mA |
Drive tray | ||
Inrush current | Controller | 1st (0-p): 30 A 2nd (0-p): 20 A 1st (0-p) time: 25 ms |
Drive tray | 1st (0-p): 30 A 2nd (0-p): 25 A 1st (0-p) time: 25 ms | |
Power cord plug type | Controller | IEC60320 C14 |
Drive tray | ||
Notes:
|
Frequency | Input Voltage (AC) | Conditions | Tolerance (%) |
60 Hz ±2 Hz | 200 V to 240 V | 1 phase 2 wire + ground | +10% or -11% |
50 Hz ±3 Hz | 200 V to 240 V | 1 phase 2 wire + ground | +10% or -11% |
Physical specifications
The following table provides the physical specifications for the VSP E1090 storage system, including weight, heat output, power consumption, and air flow specifications.
Model number | Weight (kg)2 | Heat output (W)2 | Power consumption (VA)1,2 | Air flow (m3/min)3 |
DW1000-CBLA | 54.2 | 820 | 864 | 6.0 |
DW-F850-CBLFB2 | 1 | - | - | - |
DW-F850-DBN | 14.9 | 290 | 305 | 4.1 |
DW-F1000-DBNE | 14.9 | 290 | 305 | 4.1 |
DW-F850-DBNFB2 | 0.6 | - | - | - |
DW-F1000-DBS | 17 | 116 | 126 | 2.2 |
DW-F1000-DBSE | 17 | 116 | 126 | 2.2 |
DW-F1000-DBS2 | 17 | 290 | 305 | 2.2 |
DW-F1000-DBS2E | 17 | 290 | 305 | 2.2 |
DW-F1000-DBLE | 17.4 | 124 | 144 | 2.2 |
DW-F1000-DBLE | 17.4 | 124 | 144 | 2.2 |
DW-F1000-DB60 | 36 | 184 | 191 | 5.1 |
DW-F1000-DB60E | 36 | 184 | 191 | 5.1 |
DW-F1000-DBFB60 | 1.0 | |||
DKC-F910I-ACLF | 1.2 | 18.5 | 19.5 | |
DKC-F910I-FANM | 1.1 | 21.6 | 22.7 | |
DW-F800-NMC1F | 0.15 | - | - | - |
DW-F800-SCQ1 | 0.2 | |||
DW-F800-SCQ1F | 0.2 | |||
DW-F800-SCQ3 | 0.45 | |||
DW-F800-SCQ5 | 0.6 | |||
DW-F800-SCQ5A | 0.6 | |||
DW-F800-SCQ1HA | 1.0 | |||
DKC-F910I-BN8G | 0.5 | 16.2 | 17.1 | - |
DKC-F910I-BN8GE | 0.5 | 16.2 | 17.1 | - |
DW-F1000-BS12G | 0.5 | 16 | 17.8 | - |
DW-F1000-BS12GE | 0.5 | 16 | 17.8 | - |
DW-F900-CM32G | 0.054 | 4 | 4.2 | |
DW-F900-CM64G | 0.054 | |||
DW-F1000-BM65 | 0.2 | 6.5 | 6.8 | - |
DW-F1000-BM65E | 0.2 | 6.5 | 6.8 | - |
DW-F910I-4HF32R | 0.5 | 17.9 | 19.9 | |
DW-F910I-2HS10S | 0.4 | 18.0 | 18.9 | - |
DW-F910I-2HS10B | 0.6 | 28.5 | 30.0 | - |
DKC-F810I-1PL16 | 0.02 | 0.79 | 0.88 | - |
DKC-F810I-1PS16 | 0.02 | 0.94 | 1.05 | - |
DKC-F810I-1PS32 | 0.02 | 1.29 | 1.43 | - |
DW-F1000-CHBBA | 32.7 | 222 | 230 | 2.0 |
DW-F850-CBSFB2 | 0.5 | - | - | - |
DKC-F910I-1R9RVM | 0.21 | 19.0 | 20.0 | - |
DKC-F910I-3R8RVM | 0.21 | 19.0 | 20.0 | - |
DKC-F910I-7R6RVM | 0.21 | 19.0 | 20.0 | - |
DKC-F910I-15RRVM | 0.21 | 19.0 | 20.0 | - |
DKC-F910I-30RRVM | 0.21 | 19.0 | 20.0 | - |
DKC-F810I-1R8JGM | 0.3 | 13 | 14 | - |
DKC-F810I-2R4JGM | 0.3 | 13 | 14 | - |
DKC-F810I-6R0H9M | 0.85 | 20 | 21 | - |
DKC-F810I-10RH9M | 0.77 | 20 | 21 | - |
DKC-F810I-14RH9M | 0.77 | 20 | 21 | - |
DKC-F810I-18RH9M | 0.77 | 20 | 21 | - |
DKC-F810I-1T9MGM | 0.23 | 13 | 14 | - |
DKC-F810I-3R8MGM | 0.23 | 13 | 14 | - |
DKC-F810I-7R6MGM | 0.23 | 13 | 14 | - |
DKC-F810I-15RMGM | 0.23 | 13 | 14 | - |
DKC-F810I-30RMGM | 0.23 | 13 | 14 | - |
DKC-F810I-2R4J8M | 0.4 | 13 | 14 | - |
DKC-F810I-1R8J8M | 0.4 | 13 | 14 | - |
DKC-F810I-2R4J8M | 0.4 | 13 | 14 | - |
DKC-F810I-6R0HLM | 0.96 | 20 | 21 | - |
DKC-F810I-10RHLM | 0.88 | 20 | 21 | - |
DKC-F810I-14RHLM | 0.88 | 20 | 21 | - |
DKC-F810I-18RHLM | 0.88 | 20 | 21 | - |
|