Environmental specifications for VSP G200
The environmental specifications are described for the storage system.
Environmental specifications
- DB60 dense drive tray
- Hitachi provided service processor (SVP) server
- First-generation FMDs (non-DC2 FMDs)
State |
Controller |
SFF, LFF drive trays |
Dense intermix drive tray | |
Operating | 50°F to 104°F (10°C to 40°C) | 50°F to 104°F (10°C to 40°C) | 50°F to 95°F (10°C to 35°C) | |
Non-operating | 14°F to 122°F (-10°C to 50°C) | 14°F to 122°F (-10°C to 50°C) | 14°F to 122°F (-10°C to 50°C) | |
Transport, storage | -22°F to 140°F (-30°C to 60°C) | -22°F to 140°F (-30°C to 60°C) | -22°F to 140°F (-30°C to 60°C) | |
Temperature change rate (°C/h) | 10 or less |
State |
Controller |
FMD drive trays | ||
Operating | 50°F to 104°F (10°C to 40°C) | DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed: 50°F to 95°F (10°C to 35°C) | ||
Operating | 50°F to 104°F (10°C to 40°C) | DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed: 50°F to 104°F (10°C to 40°C) | ||
Non-operating | 14°F to 122°F (-10°C to 50°C) | 14°F to 95°F (-10°C to 35°C) | ||
Transport, storage | -22°F to 140°F (-30°C to 60°C) | -22°F to 122°F (-30°C to 50°C) | ||
Temperature change rate (°C/h) | 10 or less |
State |
Percentage |
Operating | 8 to 80 |
Non-operating | 8 to 90 |
Transport, storage (%) | 5 to 95 |
Maximum wet bulb temperature (°C) | 29 (non-condensing) |
State |
m/s2 |
Operating | 2.5 or less
Within 5 seconds (resonance point: 10 Hz or less) |
Non-operating | 5.0 or less at 5 Hz to 300 Hz (no damage to product)
9.8 (1.0 G) Within 5 seconds (resonance point: 10 Hz or less) |
Transport (packed) | 5.0 or less |
State |
m/s2 |
Operating | 20 or less
(10 ms, half sine wave) |
Non-operating | 50 or less
(10 ms, half sine wave) |
Transport (packed) | 80 or less |
State |
Controller |
FMD drive | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) 900 (Environmental temperature: 10°C to 40°C) |
3,000 (Environmental temperature 10°C to 32°C) OR 900 (Environmental temperature: 10°C to 35°C) when DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed. | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) 900 (Environmental temperature: 10°C to 40°C) |
3,000 (Environmental temperature: 10°C to 32°C) OR 900 (Environmental temperature: 10°C to 40°C) when DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed. | ||
Non-operating (m) | -60 to 12,000 | N/A |
State |
Controller |
SFF and LFF drives |
Dense intermix drive tray | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) |
3,000 (Environmental temperature: 10°C to 32°C) |
3,000 (Environmental temperature: 10°C to 28°C) 1,000 (Environmental temperature: 10°C to 35°C) | ||
900 (Environmental temperature: 10°C to 40°C) |
900 (Environmental temperature: 10°C to 40°C) | ||||
Non-operating (m) | N/A |
Avoid areas exposed to corrosive gas and salty air.
State |
Controller |
SFF, LFF |
Dense intermix drive tray | |
Operating | 60 dB (Environmental temperature 32°C or less)1 | 60 dB (Environmental temperature 32°C or less)1 | 71 dB (Environmental temperature 32°C or less)1, 2, 3, 4 | |
Non-operating | 55 dB | 55 dB | 71 dB (Environmental temperature 32°C or less)1, 2, 3, 4 | |
Notes:
|
State |
Controller |
FMD | ||
Operating | 60 dB (Environmental temperature 32°C or less)1 | 60 dB (Environmental temperature 32°C or less)1,
2,
3
(When accessing the dense intermix drive tray, do not work for long times at the rear of the rack.) | ||
Non-operating | 55 dB (Environmental temperature 32°C or less)1, 2, 3, 4 55 dB | |||
Notes:
|
VSP G200 environmental specifications (DC power supply)
Item |
CBSSD/CBSLD/DBSD/DBLD |
Notes | ||
Temperature | Operating |
41°F to 104°F (5°C to 40°C) | ||
Non-operating |
23°F to 131°F (-5 to 55°C) in 16 hours | |||
Transport/storage) |
-22°F to 140°F (-30°C to 60°C) | |||
Humidity | Operating |
5% to 85% (non-condensing) | ||
Transportation/storage |
5% to 95% (non-condensing) | |||
Vibration | Operating (m/s2) |
2.5 or less (5 to 300 Hz) |
Within 5 seconds (Resonance point:10 Hz or less) | |
Non-operating (m/s2) |
5.0 or less (5 to 300 Hz): No critical damage for product. 9.8 (1.0 G) Adopt fall-prevention safety measures. | |||
Transport (packed) (m/s2) |
5.0 or less | |||
Impact | Operating (m/s2) |
20 or less |
10 ms, half sine wave | |
Non-operating (m/s2) |
50 or less | |||
Transport (packed) (m/s2) |
80 or less | |||
Angle at which the storage system turns over |
15° or less |
To be measured when installed on leveling bolts. | ||
Altitude | Operating (m) |
-60 to 1,800 above sea level Environmental temperature: 41°F to 104°F (5°C to 40°C) -1,800 to 4,000 above sea level Environmental temperature: 41°F to 86°F (5°C to 30°C) | ||
Atmosphere |
No corrosive gas and salty air must be found. | |||
Acoustic Noise | Operating |
60 dB Environmental temperature: 89.6°F (32°C) or less The system's internal temperature controls the rotating speed of the fan. Therefore, this standard value might be exceeded if the maximum load continues under high-temperature environment or if a system failure occurs. |
Measured at the position 1.5 meter away from the storage system, at a height of 1.5 meters. | |
Standby |
55 dB |