Specifications
The storage system use the following specifications.
The Hitachi Virtual Storage Platform 5000 series (VSP 5000 series) storage systems are designed to operate in a controlled environment such as a data center. The following tables provide the environmental, electrical, and physical requirements and specifications for the storage systems.
Storage system specifications
The following table lists the technical specifications of the Hitachi Virtual Storage Platform 5000 series storage system.
Item |
Specification | |||
System |
2.5-inch SAS HDD/SSD |
Maximum number of drives |
2-node system: 768 4-node system: 1,536 6-node system: 2,304 | |
3.5-inch SAS HDDs |
Maximum number of drives |
2-node system: 384 4-node system: 768 6-node system: 1,152 | ||
Number of FMDs |
Maximum number of drives |
2-node system: 192 4-node system: 384 6-node system: 576 | ||
Number of NVMe drives |
Maximum number of SSDs |
2-node system: 96 4-node system: 192 6-node system: 288 | ||
Maximum number of SCM drives |
2-node system: 33 4-node system: 66 6-node system: 99 | |||
RAID group configuration | RAID 6 |
| ||
RAID 5 |
| |||
RAID 1 (RAID 1+0) |
| |||
Maximum number of spare drives |
2-node system: 64 4-node system: 128 6-node system: 192 | |||
Maximum number of volumes |
65,280 | |||
Maximum storage system capacity (physical capacity) (30-TB 2.5-inch SAS SSDs) |
2-node system: 23.1 PB (20.5 PiB) 4-node system: 46.2 PB (41 PiB 6-node system: 69.3 PB (61.5 PiB) | |||
Maximum external configuration |
255 PiB | |||
Memory |
Cache memory capacity |
512 GiB to 6,144 GiB | ||
Storage interface |
Controller-drive box (DKC-DB) interface |
SAS/Dual Port NVMe/Dual Port (SAS and NVMe cannot be intermixed within each node pair.) | ||
Data transfer rate | SAS Interface |
12 Gbps | ||
NVMe (PCIe) Interface | 8 Gbps | |||
Maximum number of back-end modules (BEMs) (also called disk boards, or DKBs |
2-node system: 8 4-node system: 16 6-node system: 24 | |||
Device interface | Channel type | Open Systems |
Fibre Channel Shortwave Fibre Channel Longwave iSCSI (Optic) | |
Mainframe |
Fibre Channel Shortwave Fibre Channel Longwave | |||
Data trasfer rate |
Fibre Channel |
Open System: 4/8/16/32 Gbps Mainframe: 4/8/16 Gbps | ||
iSCSI (Optic) |
10 Gbps | |||
Maximum number of CHB |
2-node system: 16 2-node system: 32 6-node system: 48 |
Physical specifications
The following table provides power consumption, heat output, and airflow specifications of the individual Virtual Storage Platform 5000 series system components.
Component |
Component model number |
Maximum power consumption (VA) |
Maximum heat output | Airflow (m3/min) * |
Weight (kg) |
Primary controller chassis | DKC910I-CBX | 920 | 874 | 5.4 | 70.0 |
Primary controller chassis | DKC910I-CBXCL | 881 | 838 | 5.4 | 70.4 |
Secondary controller chassis | DKC-F910I-CBX2 | 469 | 446 | 3.0 | 41.6 |
Secondary controller chassis | DKC-F910I-CBXCL2 | 430 | 409 | 3.0 | 42.0 |
SFF drive chassis |
DKC-F910I-SBX |
1,221 |
1,160 |
12.8 |
68 |
LFF drive chassis |
DKC-F910I-UBX |
1,000 |
920 |
18.9 |
126.0 |
FMD Drive Chassis |
DKC-F910I-FBX |
620 |
590 |
6.4 |
76.7 |
Controller Chassis Bezel |
DKC-F910I-CBLFB |
- |
- |
- |
1.0 |
Controller Chassis Bezel |
DKC-F910I-CBLFBA |
- |
- |
- |
1.2 |
Drive Chassis Bezel |
DKC-F910I-DBFB |
- |
- |
- |
0.5 |
Drive Chassis Bezel |
DKC-F910I-DBFBA |
- |
- |
- |
0.5 |
HSN Chassis Bezel |
DKC-F910I-HSNFB |
- |
- |
- |
0.6 |
HSN Chassis Bezel |
DKC-F910I-HSNFBA |
- |
- |
- |
0.6 |
Flash Module Bezel |
DKC-F910I-FBFB |
- |
- |
- |
0.7 |
Flash Module Bezel |
DKC-F910I-FBFBA |
- |
- |
- |
0.9 |
Additional Service Processor |
DKC-F910I-SVP |
16.0 |
15.2 |
- |
0.7 |
Additional RAID Controller Kit | DKC-F910I-CTL | 390 | 370 |
- | 11.4 |
Additional RAID Controller Kit | DKC-F910I-CTLCL | 351 | 333 | - | 11.8 |
RAID Controller Upgrade Kit | DKC-F910I-CTLUG | 260 | 247 | - | 6.6 |
Compression Accelerator Fan Module | DKC-F910I-ACLF | 19.5 | 18.5 | - | 1.2 |
Power Supply Unit | DKC-F910I-CBPSU | - | - | - | 2.2 |
Safety Cover for empty CTL slot | DKC-F910I-SCFC |
- |
- |
- | 1.8 |
Additional Hub |
DKC-F910I-HUB |
12.0 |
11.4 |
- |
0.5 |
Fan Module |
DKC-F910I-FANM |
22.7 |
21.6 |
- |
1.1 |
Operation Panel Kit |
DKC-F910I-OPPNL |
1.0 |
1.0 |
- |
0.37 |
Mainframe Fibre 4-port 16G Host Adapter for Shortwave |
DKC-F910I-4MS16 |
23.5 |
22.3 |
- |
0.5 |
Mainframe Fibre 4-port 16G Host Adapter for Longwave |
DKC-F910I-4ML16 |
23.5 |
22.3 |
- |
0.5 |
Fibre 4-port 32Gbps Ready Host Adapter |
DKC-F910I-4HF32R |
24.9 |
22.4 |
- |
0.5 |
iSCSi 2-port 10G Host Adapter |
DKC-F910I-2HS10S |
22.8 |
21.6 |
- |
0.5 |
SFP for 16Gbps Longwave |
DKC-F810I-1PL16 |
- |
- |
- |
0.02 |
SFP for 16Gbps Shortwave |
DKC-F810I-1PS16 |
- |
- |
- |
0.02 |
SFP for 32Gbps Longwave |
DKC-F810I-1PL32 |
- |
- |
- |
0.02 |
SFP for 32Gbps Shortwave |
DKC-F810I-1PS32 |
- |
- |
- |
0.02 |
Disk Adapter |
DKC-F910I-BS12G |
17.2 |
16.0 |
- |
0.5 |
Encryption Disk Adapter |
DKC-F910I-BS12GE |
17.2 |
16.0 |
- |
0.5 |
Cache Memory 64GB | DW-F850-CM64GL | 5.0 | 4.8 | - |
0.054 |
Cache Memory 32GB |
DW-F850-CM32G |
4.2 |
4.0 |
- |
0.054 |
Cache Memory 64GB |
DW-F850-CM64G |
5.0 |
4.8 |
- |
0.054 |
Cache Flash Memory 45 |
DKC-F910I-BM45 |
6.8 |
6.5 |
- |
0.2 |
Cache Flash Memory 45 with encryption |
DKC-F910I-BM4E |
6.8 |
6.5 |
- |
0.2 |
Cache Flash Memory 95 | DKC-F910I-BM95 |
6.8 |
6.5 |
- |
0.2 |
Cache Flash Memory 95 with encryption | DKC-F910I-BM9E |
6.8 |
6.5 |
- |
0.2 |
Rack Rail |
A34V-600-850-UNI-S.P |
- |
- |
- |
- |
HSN Chassis Rail |
3292455-001 |
- |
- |
- |
- |
Rack Rail |
A34V-600-850-UNI-S.P |
- |
- |
- |
- |
Drive Chassis Rail for FBX |
A3BF-HK-GL-740-1-S.P L |
- |
- |
- |
- |
PCIe Cable set for primary module CBXA |
DKC-F910I-MCC1 |
- |
- |
- |
0.1 |
PCIe Cable set for primary module CBXB |
DKC-F910I-MCC2 |
- |
- |
- |
0.1 |
PCIe Cable 5m |
DKC-F910I-MFC5 |
- |
- |
- |
0.2 |
PCIe Optical Module |
DKC-F910I-PQSFP |
- |
- |
- |
0.005 |
SAS Optical Module |
DKC-F910I-SQSFP |
- |
- |
- |
0.005 |
Optical Cable 10m |
DKC-F910I-MPC10 |
- |
- |
- |
0.2 |
Optical Cable 20m |
DKC-F910I-MPC20 |
- |
- |
- |
0.3 |
Optical Cable 30m |
DKC-F910I-MPC30 |
- |
- |
- |
0.4 |
Optical Cable 100m |
DKC-F910I-MPC1H |
- |
- |
- |
1.0 |
SAS Cable set for Disk Adapter |
DKC-F910I-SCCS |
- |
- |
- |
1.4 |
QSFP Metal Cable 1m |
DW-F800-SCQ1 |
- |
- |
- |
0.2 |
QSFP Metal Cable 1.5m |
DW-F800-SCQ1F |
- |
- |
- |
0.2 |
RJ45 bundled LAN Cable Kit |
DKC-F910I-LC |
- |
- |
- |
0.2 |
RJ45 Cable 5m |
DKC-F910I-LC5 |
- |
- |
- |
0.3 |
RJ45 Cable 10m |
DKC-F910I-LC10 |
- |
- |
- |
0.5 |
RJ45 Cable 20m |
DKC-F910I-LC20 |
- |
- |
- |
0.9 |
RJ45 Cable 30m |
DKC-F910I-LC30 |
- |
- |
- |
1.4 |
RJ45 Cable 100m |
DKC-F910I-LC1J |
- |
- |
- |
4.7 |
SFF 2.4TB Disk Drive |
DKC-F810I-2R4JGM |
14.0 |
13.0 |
- |
0.26 |
LFF 14TB Disk Drive |
DKC-F810I-14RH9M |
21.0 |
20.0 |
- |
0.77 |
LFF 18TB Disk Drive | DKC-F810I-18RH9M |
21.0 |
20.0 |
- |
0.77 |
SFF 960GB SSD Drive |
DKC-F810I-960MGM |
14.0 |
13.0 |
- |
0.21 |
SFF 1.9TB SSD Drive |
DKC-F810I-1T9MGM |
14.0 |
13.0 |
- |
0.21 |
SFF 3.8TB SSD Drive |
DKC-F810I-3R8MGM |
14.0 |
13.0 |
- |
0.21 |
SFF 7.6TB SSD Drive |
DKC-F810I-7R6MGM |
14.0 |
13.0 |
- |
0.21 |
SFF 15TB SSD Drive |
DKC-F810I-15RMGM |
14.0 |
13.0 |
- |
0.21 |
SFF 30TB SSD Drive | DKC-F810I-30RMGM |
14.0 |
13.0 |
- |
0.21 |
7TB Flash Module Drive |
DKC-F810I-7R0FP |
30.0 |
28.0 |
- |
1.4 |
14TB Flash Module Drive |
DKC-F810I-14RFP |
30.0 |
28.0 |
- |
1.4 |
NVMe Disk Adapter |
DKC-F910I-BN8G |
21.5 |
20.5 |
- |
0.5 |
NVMe Disk Adapter |
DKC-F910I-BN8GE |
21.5 |
20.5 | 0.5 | |
NVMe SFF Drive Chassis |
DKC-F910I-NBX |
1221 |
1160 |
16.4 |
62 |
NVMe Chassis Rail |
A3BF-HK-GL-740-1-S.P |
- |
- |
- |
- |
NVMe Cable set for NVMe Disk Adapter |
DKC-F910I-NCCS |
- |
- |
- |
1.1 |
SFF 1.9TB NVMe Drive |
DKC-F910I-1R9RVM |
20 |
19 |
- |
0.21 |
SFF 3.8TB NVMe Drive |
DKC-F910I-3R8RVM |
20 |
19 |
- |
0.21 |
SFF 7.6TB NVMe Drive |
DKC-F910I-7R6RVM |
20 |
19 |
- |
0.21 |
SFF 15TB NVMe Drive |
DKC-F910I-15RRVM |
20 |
19 |
- |
0.21 |
SFF 30TB NVMe Drive |
DKC-F910I-30RRVM |
20 |
19 |
- |
0.21 |
SCM 375GB NVMe Drive | DKC-F910I-375YVM |
20 |
19 |
- |
0.19 |
* Maximum values when all fans rotate at the maximum speed |
Electrical specifications
The Hitachi Virtual Storage Platform 5000 series storage system power distribution units (PDUs) support single-phase AC power.
The Hitachi rack comes with either two, four, or six PDUs, depending on the PDU model selected. The PDUs are installed vertically in the rack.
- If two PDUs are selected, one will be installed on the left side of the rack and the other will be installed on the right side.
- If four PDUs are selected, the PDUs will be half-length and mounted vertically, one above the other, with two on the left side of the rack and two on the right side.
- If six PDUs are selected, the PDUs will be 1/3-length and mounted vertically, one above the other, with three on the left side of the rack and two on the right side.
If you need assistance using this tool, contact Hitachi Vantara Support athttps://support.hitachivantara.com/en/contact-support.html .
Item | Input Power | Inrush Current (Rating) * | Leakage Current | Inrush Current | |||
When one PS is operating | When two PSs are operating | 1st (0-p) | 2nd (0-p) | 1st (0-p) Time (-25%) | |||
Node power supply | Single phase, AC200V to AC240V | 7.2 A | 3.6 A | 1.75 mA | 30 A | 30 A | 25 ms |
DBPS (DBS2) | 3.2 A | 1.6 A | 1.75 mA | 30 A | 30 A | 25 ms | |
DBPS (DBL) | 2.0 A | 1.0 A | 1.75 mA | 30 A | 30 A | 25 ms | |
DBPS (DBF3) | 3.1 A | 1.55 A | 1.75 mA | 20 A | 15 A | 80 ms | |
DBPS (DBN) | 4.0 A | 2.0 A | 1.75 mA | 30 A | 30 A | 25 ms | |
Node interconnect switch power supply | 1.2 A | 0.6 A | 1.75 mA | 30 A | 30 A | 25 ms | |
* When two power supplies are operating, each power supply provides about half of the required power for the storage system. When only one of the two power supplies is operating, the power supply provides all required power for the storage system. Therefore, use the power supplies that meet the rated input current for when one power supply is operating. |
The following table shows the supported input voltage and frequency for the controller chassis, drive box, and node interconnect switch.
Input voltage | Voltage tolerance | Frequency | Wire connection |
200V to 240V | +10% or -11% |
50Hz ± 2Hz 60Hz ± 2Hz | 1 Phase 2 Wire + Ground |
|
Environmental specifications
The following table lists the environmental specifications for the Hitachi Virtual Storage Platform 5000 series storage systems.
Item |
Condition | ||
Operating |
Not operating |
Shipping and storage | |
Temperature range |
10ºC to 40ºC6 |
-10ºC to 50ºC |
-30ºC to 60ºC |
Relative Humidity (No dew condensation) |
8% to 80% |
8% to 90% |
5% to 95% |
Max. Wet Bulb |
29ºC |
29ºC |
29ºC |
Temperature gradient per hour |
10ºC |
10ºC |
10ºC |
Dust |
0.15 or less |
- |
- |
Gaseous contaminants2 |
G1 classification levels | ||
Altitude (m) |
~ 3,050 (10ºC ~ 28ºC) ~ 950 (10ºC ~ 40ºC)6 |
-60 to 3,000 |
-60 to 3,000 |
Noise Level (Recommended) |
90 dB or less1 |
- |
- |
Chassis Acoustic Level 45 |
|
|
- |
|
Mechanical environmental specifications
The following tables list the mechanical environmental conditions for the Hitachi Virtual Storage Platform 5000 series storage systems.
Item |
In operation |
In non-operation | |
Vibration value of storage system |
0.25Grms, 5-500Hz, 30min. |
0.6Grms, 3-500Hz, 30min. | |
Vibration value of chassis |
- |
|