Power distribution units for Universal V3 Rack
The Hitachi Universal V3 Rack is equipped with power distribution units (PDUs) that are appropriate for the planned rack installation location: Americas, Asia-Pacific and China (APAC), or Europe-Middle East-Africa (EMEA).. The PDUs can provide electrical power to the racked system in a single-phase or three-phase configuration.
- Before installing third-party devices into the rack, check the electrical current draw of each device. Verify the electrical specifications and allowable current load on each PDU before plugging the device into the PDU.
- Balance the electrical current load between available PDUs.
Americas single-phase PDU 1P30A-10C13-2C19-UL20A.P
The following figure shows the Americas single-phase PDU, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
1P30A-10C13-2C19-UL20A.P |
3/side 6/rack |
Single phase 208V, 30A (20A rated) 60Hz Delta/wYe: N/A NEMA L6-30P input power plug 4.5 m (14.76 feet) cable |
10 C13 + 2 C19 sockets Max allowable current: 24A 5kVA | 72A (14.4kVA) |
Housing Length: 594 mm (23.4 in.) Weight: 3.1 kg (6.8 lbs) |
Americas three-phase PDU 3P30A-8C13-3C19-UL20A.P
The following figure shows the Americas three-phase PDU with 8 C13 sockets and 3 C19 sockets, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
3P30A-8C13-3C19-UL20A.P |
3/side 6/rack |
Three phase 208V 3P, 30A (20A rated) 60Hz Delta/wYe: Delta NEMA L15-30P input power plug 4.5 m (14.76 feet) cable |
8 C13 + 3 C19 sockets Max allowable current: 41.6A 14.4kVA | 124.7A (43.1kVA) |
Housing Length: 611 mm (24 in.) Weight: 3.7 kg (8.2 lbs) |
Americas three-phase PDU 3P30A-15C13-3C19-UL20A.P
The following figure shows the Americas three-phase PDU with 15 C13 sockets and 3 C19 sockets, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
3P30A-15C13-3C19-UL20A.P |
2/side 4/rack |
Three phase 208V 3P, 30A (20A rated) 60Hz Delta/wYe: Delta NEMA L15-30P input power plug 4.5 m (14.76 feet) cable |
15 C13 + 3 C19 sockets Max allowable current: 41.6A 14.4kVA | 83.1A (28.7kVA) |
Housing Length: 893 mm (35.2 in.) Weight: 4.2 kg (9.3 lbs) |
APAC and EMEA single-phase PDU 1P32A-10C13-2C19-CE20A.P
The following figure shows the APAC and EMEA single-phase PDU, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
1P32A-10C13-2C19-CE20A.P |
3/side 6/rack |
Single phase 230V max. 32A (20A rated) 50Hz / 60Hz Delta/wYe: N/A CEE-plug 32A 3-poles input power plug 4.5 m (14.76 feet) cable |
10 C13 + 2 C19 sockets Max allowable current: 25.6A 5.6kVA | 76.8A (16.8kVA) |
Housing Length: 554 mm (21.8 in.) Weight: 2.5 kg (5.5 lbs) |
APAC and EMEA three-phase PDU 3P16A-9C13-3C19-CE20A.P
The following figure shows the APAC and EMEA three-phase PDU with 9 C13 sockets and 3 C19 sockets, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
3P16A-9C13-3C19-CE20A.P |
3/side 6/rack |
Three phase 400V max. 16A (20A rated) 50Hz / 60Hz Delta/wYe: wYe CEE-plug 16A 5-poles input power plug 4.5 m (14.76 feet) cable |
9 IEC C13 + 3 IEC C19 sockets Max allowable current: 38.4A 25.3kVA | 115A (76kVA) |
Housing Length: 596 mm (23.5 in.) Weight: 2.6 kg (5.7 lbs) |
APAC and EMEA three-phase PDU 3P32A-24C13-6C19-CE20A.P
The following figure shows the APAC and EMEA three-phase PDU with 24 C13 sockets and 6 C19 sockets, and the following table provides the electrical specifications for this PDU.
Part number |
Maximum number of PDUs |
Power input per PDU |
Power output per PDU |
Total rack amperage available | Dimensions |
3P32A-24C13-6C19-CE20A.P |
3/side 6/rack |
Three phase 400V max. 32A (20A rated) 50Hz / 60Hz Delta/wYe: wYe CEE-plug 32A 5-poles input power plug 4.5 m (14.76 feet) cable |
24 IEC C13 + 6 IEC C19 sockets Max allowable current: 77A 50.8kVA | 77A (50.8kVA) |
Housing Length: 1376 mm (54.2 in.) Weight: 4.8 kg (10.6 lbs) |