Skip to main content

We've Moved!

Product Documentation has moved to docs.hitachivantara.com
Hitachi Vantara Knowledge

Power distribution units for Universal V2B Rack

The Universal V2B Rack is equipped with specific power distribution units (PDU) for Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the racked system in a single-phase or three-phase configuration.

Caution
  • Before installing third-party devices into the rack, check the electrical current draw of each device. Verify the electrical specifications and allowable current load on each PDU before plugging the device into the PDU.
  • Balance the electrical current load between available PDUs.

Americas single-phase PDU 1P30A-8C13-3C19UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU 1P30A-8C13-3C19UL.P)
GUID-F77DBF81-9403-42CA-B4A2-EBC99F103ADF-low.png

Part Number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

1P30A-8C13-3C19UL.P

Americas

6/rack

3/side

Single phase

208V, 30A (24A rated) 60Hz

Delta/wYe: N/A

NEMA L6-30P input power plug

4.5 m (14.76 feet) cable

8 IEC C13 + 3 IEC C19 sockets

Max allowable current: 24A

5kVA

72A (15kVA)

Americas single-phase PDU 1P30A-15C13-3C19UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU 1P30A-15C13-3C19UL.P)
GUID-37B58566-8352-4E9B-BB52-66C2BE471D86-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

1P30A-15C13-3C19UL.P

Americas

4/rack

2/side

Single phase

208V, 30A (24A rated) 60Hz

Delta/wYe: N/A

NEMA L6-30P input power plug

4.5 m (14.76 feet) cable

15 IEC C13 + 3 IEC C19 sockets

Max allowable current: 24A

5kVA

48A (10kVA)

Americas three-phase PDU 3P30A-8C13-3C19UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-8C13-3C19UL.P)
GUID-79550C39-82B3-476D-8F56-7EC2681BA4E4-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P30A-8C13-3C19UL.P

Americas

6/rack

3/side

Three phase

208V 3P, 30A (24A rated) 60Hz

Delta/wYe: Delta

NEMA L15-30P input power plug

4.5 m (14.76 feet) cable

8 IEC C13 + 3 IEC C19 sockets

Max allowable current: 38.4A

8kVA

115A (24kVA)

Americas three-phase PDU 3P30A-15C13-3C19UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-15C13-3C19UL.P)
GUID-B75C9E98-8E3B-4CD6-A941-3542C12F1BF8-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P30A-15C13-3C19UL.P

Americas

4/rack

2/side

Three phase

208V 3P, 30A (24A rated) 60Hz

Delta/wYe: Delta

NEMA L15-30P input power plug

4.5 m (14.76 feet) cable

15 IEC C13 + 3 IEC C19 sockets

Max allowable current: 38.4A

8kVA

77A (16kVA)

Americas three-phase PDU 3P30A-24C13-6C19UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU 3P30A-24C13-6C19UL.P)
GUID-6F5710C7-B359-47F0-B887-52D929040723-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P30A-24C13-6C19UL.P

Americas

2/rack

1/side

Three phase

208V 3P, 30A (24A rated) 60Hz

Delta/wYe: Delta

NEMA L15-30P input power plug

4.5 m (14.76 feet) cable

24 IEC C13 + 6 IEC C19 sockets

Max allowable current: 38.4A

8kVA

38.4A (8kVA)

APAC and EMEA single-phase PDU 1P32A-9C13-3C19CE.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Single-phase 1P32A-9C13-3C19CE.P)
GUID-49BFFA89-FCF6-41E0-A77C-A7B4F1514818-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

1P32A-9C13-3C19CE.P

APAC and EMEA

6/rack

3/side

Single phase

230V max. 32A (25.6A rated) 50Hz / 60Hz

Delta/wYe: N/A

IEC309 P + N + E input power plug

4.5 m (14.76 feet) cable

9 IEC C13 + 3 IEC C19 sockets

Max allowable current: 25.6A

5.9kVA

77A (17.6kVA)

APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Single-phase 1P32A-18C13-3C19CE.P)
GUID-EA3CA8C6-50CA-47C3-A0D1-142A0F3426B3-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

1P32A-18C13-3C19CE.P

APAC and EMEA

4/rack

2/side

Single phase

230V max. 32A (25.6A rated) 50Hz / 60Hz

Delta/wYe: N/A

IEC309 P + N + E input power plug

4.5 m (14.76 feet) cable

18 IEC C13 + 3 IEC C19 sockets

Max allowable current: 38.4A

8.8kVA

77A (17.6kVA)

APAC and EMEA three-phase PDU 3P16A-9C13-3C19CE.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P16A-9C13-3C19CE.P)
GUID-627BAD6A-C3AF-497E-9708-F3056C8419BE-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P16A-9C13-3C19CE.P

APAC and EMEA

6/rack

3/side

Three phase

400V max. 16A (12.8A rated) 50Hz / 60Hz

Delta/wYe: wYe

IEC309 3P + N + E input power plug

4.5 m (14.76 feet) cable

9 IEC C13 + 3 IEC C19 sockets

Max allowable current: 38.4A

8.8kVA

115A (26.4kVA)

APAC and EMEA three-phase PDU 3P16A-15C13-3C19CE.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P16A-15C13-3C19CE.P)
GUID-D2D79840-F6A1-46D8-B55E-152786439FDA-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P16A-15C13-3C19CE.P

APAC and EMEA

4/rack

2/side

Three phase

400V max. 16A (12.8A rated) 50Hz / 60Hz

Delta/wYe: wYe

IEC309 3P + N + E input power plug

4.5 m (14.76 feet) cable

15 IEC C13 + 3 IEC C19 sockets

Max allowable current: 38.4A

8.8kVA

77A (17.6kVA)

APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P32A-24C13-6C19CE.P)
GUID-35FDB085-FA44-44B5-BAB1-A88CC6ECBBF6-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P32A-24C13-6C19CE.P

APAC and EMEA

2/rack

1/side

Three phase

400V max. 32A (25.6A rated) 50Hz / 60Hz

Delta/wYe: wYe

IEC309 3P + N + E input power plug

4.5 m (14.76 feet) cable

24 IEC C13 + 6 IEC C19 sockets

Max allowable current: 77A

17.6kVA

77A (17.6kVA)

Americas, APAC, and EMEA three-phase PDU 3P30A-243-69CE-UL.P

The following figure and table describe the specifications of the PDU.

Figure 1: APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase 3P30A-243-69CE-UL.P)
GUID-BE324C62-730E-44FF-9221-0E572DFB3EF5-low.png

Part number

Region

Quantity

Power input per PDU

Power output per PDU

Total rack amperage available

3P30A-243-69CE-UL.P

Americas, APAC, and EMEA

2/rack

1/side

Three phase

400/415V max. 30/32A (24A rated) 50Hz / 60Hz

Delta/wYe: wYe

IEC309 3P + N + E input power plug

4.5 m (14.76 feet) cable

24 IEC C13 + 6 IEC C19 sockets

Max allowable current: 77A

17.6kVA

77A (17.6kVA)

 

  • Was this article helpful?