Skip to main content

We've Moved!

Product Documentation has moved to docs.hitachivantara.com
Hitachi Vantara Knowledge

Electrical specifications for VSP G200

The electrical specifications are described for the storage system.

Electrical specifications

Item

Controller

Drive tray

Input voltage (operable voltage range) (V)

AC 100-120/200-240 +6%/-11%

SFF, LFF, FMD, and dense intermix drive tray: AC 200-240 +6%/-11%

Frequency (Hz) 50/60 ±1
Number of phases, cabling Single-phase with protective grounding
Steady-state current 100V/200V1, 2

CBSS: 4.0x2/2.0x2

CBSL: 4.0x2/2.0x2

SFF drive tray: 2.4x2/1.2x2

LFF drive tray: 1.9x2/1.0x2

FMD drive tray: 2.6x2/1.3x2

Dense intermix drive tray: -/3.0x2

Current rating of breaker/fuse (A) 16.0 (each electrical)
Heat value (normal) (kJ/h)

CBSS: 1800 or less

CBSL 1550 or less

SFF drive tray: 1120 or less

LFF drive tray: 940 or less

FMD drive tray: 1300/1520 or less

Dense intermix drive tray: 3460 or less

Steady-state power (VA/W)3

CBSS: 800/760 or less

CBSL: 800/760 or less

SFF drive tray: 480/460 or less

LFF drive tray: 380/350 or less

FMD drive tray: 520/490 or less

Dense intermix drive tray: 1200/1160 or less

Power consumption (VA/W)

CBSS: 520/500 or less

CBSL: 450/430 or less

SFF drive tray: 320/310 or less

LFF drive tray: 280/260 or less

FMD drive tray: 440/420 or less

Dense intermix drive tray: 1000/960 or less

Notes:

  1. The power current of Nx2 described in this table is required for a single power unit.
  2. If one power unit fails, another power unit requires electric current for the two power units. Therefore, plan the power supply facility so that the current-carrying capacity for one power unit can provide the total capacity for two power units.
  3. This table shows the power requirement (100 V or 200 V) for the maximum configuration . The actual required power might exceed the value shown in the table when the tolerance is included.

VSP G200 electrical specifications (DC power supply)

Input power specifications

Item

CBSSD

CBSLD

DBSD

DBLD

Rated input voltage (v) DC -60 to -48
Input voltage fluctuation (v) DC -72 to -40
Input voltage instant fluctuation (v) DC -75 to -36
Inrush current (v) 35 (Ta = 25°C, in the range of rated input voltage, except when voltage fluctuates)
Input shape Connection by connector. Connect the terminal by the dedicated cable with terminal. Connector: Positronic Industries Inc., PCS Series
Heat value (kJ/h) 1800 1550 1120 940
Steady-state power (W) 760 760 460 350
Power consumption (W) 500 430 310 260
Input current (A) 15.9 15.9 9.6 7.3
UPS No connection
Remote adapter No connection

 

  • Was this article helpful?