Skip to main content

We've Moved!

Product Documentation has moved to docs.hitachivantara.com
Hitachi Vantara Knowledge

Electrical specifications for VSP F800

The electrical specifications are described for the storage system.

Electrical specifications

Item

Controller

Drive tray

Frequency (Hz) 50/60 ±1
Number of phases, cabling Single-phase with protective grounding
Steady-state current 100V/200V1, 2

CBLH: 4.0x2

FMD drive tray: 2.6x2/1.3x2

Current rating of breaker/fuse (A) 16.0 (each electrical)
Heat value (normal) (kJ/h)

2810 or less

FMD drive tray: 1520 or less

FMD drive tray: 1520 or less

Steady-state power (VA/W)3

CBLH: 1600/1560 or less

FMD drive tray: 520/490 or less

Power consumption (VA/W)

CBLH: 840/780 or less

FMD drive tray: 440/420 or less

Notes:

  1. The power current of Nx2 described in this table is required for a single power unit.
  2. If one power unit fails, another power unit requires electric current for the two power units. Therefore, plan the power supply facility so that the current-carrying capacity for one power unit can provide the total capacity for two power units.
  3. This table shows the power requirement (100 V or 200 V) for the maximum configuration . The actual required power might exceed the value shown in the table when the tolerance is included.

 

  • Was this article helpful?