Environmental specifications for VSP F400, F600

The environmental specifications are described for the storage systems.

Environmental specifications

Temperature

CautionThe following VSP Gx00/Fx00 storage system components are not supported in high-temperature environments. Do not operate the following components at temperatures of 40°C or higher:
  • DB60 dense drive tray
  • Hitachi provided service processor (SVP) server
  • First-generation FMDs (non-DC2 FMDs)

State

Controller

FMD drive trays

Operating 50°F to 104°F (10°C to 40°C) DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed: 50°F to 104°F (10°C to 40°C)
Non-operating 14°F to 122°F (-10°C to 50°C) 14°F to 95°F (-10°C to 35°C)
Transport, storage -22°F to 140°F (-30°C to 60°C) -22°F to 122°F (-30°C to 50°C)
Temperature change rate (°C/h) 10 or less
Humidity

State

Percentage

Operating 8 to 80
Non-operating 8 to 90
Transport, storage (%) 5 to 95
Maximum wet bulb temperature (°C) 29 (non-condensing)
Vibration

State

m/s2

Operating 2.5 or less

Within 5 seconds (resonance point: 10 Hz or less)

Non-operating 5.0 or less at 5 Hz to 300 Hz (no damage to product)

9.8 (1.0 G)

Within 5 seconds (resonance point: 10 Hz or less)

Transport (packed) 5.0 or less
Impact
State

m/s2

Operating 20 or less

(10 ms, half sine wave)

Non-operating 50 or less

(10 ms, half sine wave)

Transport (packed) 80 or less
Altitude

State

Controller

FMD drive

Operating (m)

3,000 (Environmental temperature: 10°C to 32°C)

900 (Environmental temperature: 10°C to 40°C)

3,000 (Environmental temperature: 10°C to 32°C)

OR

900 (Environmental temperature: 10°C to 40°C) when DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed.

Non-operating (m) -60 to 12,000 N/A
Atmosphere

Avoid areas exposed to corrosive gas and salty air.

Acoustic Noise
State

Controller

FMD

Operating 60 dB (Environmental temperature 32°C or less)1 60 dB (Environmental temperature 32°C or less)1, 2, 3
Non-operating 55 dB (Environmental temperature 32°C or less)1, 2, 3, 4 55 dB

Notes:

  1. The system's internal temperature controls the rotating speed of the fan module. Therefore, this standard value might be exceeded if the maximum load continues under high-temperature environment or if a failure occurs in the system.
  2. Sound pressure level (LA) changes from 66 dB or 75 dB, according to the ambient temperature, drive configuration, and operating status. Maximum volume can reach 79 dB during maintenance procedure for a failed ENC or power supply.
  3. Acoustic power level (LwA) measured by the ISO 7779 standard is 7.2 B. This value changes from 7.2 B to 8.1 B, according to the ambient temperature, drive configuration, and operating status.

 