System components and specifications
Storage system components
The Hitachi Virtual Storage Platform G200, G400, G600, G800 storage systems and Hitachi Virtual Storage Platform F400, F600, F800 all-flash arrays are modular, rack-mountable systems that incorporate state-of-the-art virtualization, data-management, and fault-tolerant technologies.
All models are compatible with most industry-standard 4-post EIA 19-inch racks with square mounting holes. The storage system can be factory-configured and shipped in a Hitachi 600 x 1200 mm V2 Universal Rack, or shipped without a rack for customer installation into an existing rack.
The Hitachi rack comes with either two or four Power Distribution Units (PDUs), depending on the PDU model selected. The PDUs are installed vertically in the rack.
- If two PDUs are selected, one will be installed on the left side of the rack and the other will be installed on the right side.
- If four PDUs are selected, the PDUs will be half-length and mounted vertically, one above the other, with two on the left side of the rack and two on the right side.
All storage systems are comprised of controllers, drive trays, and a service processor (SVP).
The controllers for the Hitachi Virtual Storage Platform G200 include either 24 2.5-inch small form-factor (SFF) disk drives or 12 3.5-inch large form-factor (LFF) disk drives.
Drive trays are intelligent and compact storage units, with each capable of holding a large numbers of disk drives in a small rack space (EIA-standard rack units). VSP G200, G400, G600, G800 storage systems support the following drive trays and drives:
- DW-F800-DBS: 2U drive tray that holds 24 2.5-inch SFF disk drives. Drives are arranged vertically in a single row.
- DW-F800-DBL: 2U drive tray that holds 12 3.5-inch LFF disk drives. Drives are arranged horizontally, with four columns of three disk drives.
- DW-F800-DBF: 2U drive tray that holds 12 Hitachi Accelerated Flash (HAF) or DC2 flash module drives. Drives are arranged horizontally, with three columns of three disk drives.
- DW-F800-DB60: 4U dense drive tray that holds 60 LFF disk drives. Drives are arranged horizontally, with five rows of 12 disk drives.
VSP F400, F600, F800 all-flash array models support various fixed storage capacity configurations of DC2 flash module drives within the DW-F800-DBF drive tray. To deliver consistent low latency host response times and highest IOP performance across all host connection ports, no HDDs are included or permitted to be configured as part of the all-flash array configurations.
Some storage systems support NAS modules for sharing file-based information over an IP network using system protocols such as Common Internet File System (CIFS), Network File System (NFS), and Server Message Block (SMB). NAS modules are installed in pairs.
The service processor (SVP) provides out‑of‑band configuration and management of the storage system, and collects performance data for key components to enable diagnostic testing and analysis. The SVP operates independently from the storage system's CPU and operating system.
The SVP is available as a physical device or as a software application.
The physical SVP is supplied by Hitachi Vantara and runs Windows Embedded Standard 7. When shipped in the Hitachi Universal V2 rack, the physical SVP is installed above the controller and drive trays. The Hitachi-supplied SVP can be configured to operate in a bridged or non-bridged network environment.
The SVP software application can run one of the following 64-bit operating systems on customer-supplied server hardware, a VMware ESXi host, or a Linux KVM host:
- Windows 7 Professional x64 Service Pack 1
- Windows 10 Professional
- Windows 10 Enterprise
- Windows Server 2012
- Windows Server 2012 R2
The SVP software application can also run a customer-supplied version of Microsoft Hyper-V Server 2012 R2 on one of the following 64-bit operating systems:
- Windows 10 Professional
- Windows 10 Enterprise
- Windows Server 2012
- Windows Server 2012 R2
VSP G200VSP G400, G600 VSP G800 VSP F400, F600 VSP F800 storage system components
The VSP G200VSP G400, G600 VSP G800 VSP F400, F600 VSP F800 includes essential building blocks such as controllers, drive trays, and other optional front and back end components.
Replacement parts
Part replacement is essential for maintaining the high performance of the system. Replacing system components is covered by the maintenance service contract.
Battery unit
Three years.
Use the storage system in a place where the ambient temperature is 86°F (30°C) or less on average.
Periodic parts replacement is required. For customers with maintenance service contracts, parts are replaced periodically in keeping with the terms of the contract.
VSP G200VSP G400, G600 VSP G800 VSP F400, F600 VSP F800 storage system mechanical specifications
The storage system mechanical specifications are described for VSP G200 VSP G400, G600 VSP G800 VSP F400, F600 VSP F800.
VSP G200 mechanical specifications (AC power supply model)
Controller
1 CBSS
1 CBSL
Drive trays
1 SFF drive tray (DBS)
1 LFF drive tray (DBL)
1 FMD drive tray
1 dense intermix drive tray
Item |
Component |
Specification |
Drive size (WxDxH) | CBSS, SFF drive tray |
2.5-type: 3.21 x 8.10 x 0.74 inches (81.6 x 205.7 x 18.7 mm) |
CBSL, LFF drive tray |
3.5-type: 4 x 5.78 x 1.02 inches (101.6 x 147.0 x 26.1 mm) | |
FMD drive tray |
Flash module drive: 5.74 x 14.44 x 0.78 inches (146 x 366.8 x 19.8 mm) | |
Data capacity (GB) | CBSS, SFF drive tray |
2.5-type: 196.92, 288.20, 393.85, 576.39, 1152.79, 1729.29, 1890.46 |
CBSL, LFF drive tray, dense intermix drive tray |
3.5-type: 393.85, 1152.79, 1729.29, 3916.14, 5874.22, 9790.36 | |
FMD drive tray |
Flash module drive: 1759.21, 3518.43 , 7036.87, 14073.74 GB | |
Rotational speed (min-1) | CBSS, SFF drive tray |
Flash drive, 2.5-type: 196.92 GB, 393.85 GB 2.5-type: 288.20 GB, 15,000 RPM 2.5-type: 576.39 GB, 10,000 or 15,000 RPM 2.5-type: 1152.79 GB, 10,000 RPM 2.5-type: 1729.29 GB, 10,000 RPM |
CBSL, LFF drive tray |
Flash drive, 3.5-type: 393.85 GB 3.5-type: 1152.79 GB, 10,000 RPM 3.5-type: 1729.29 GB, 10,000 RPM 3.5-type: 3916.14 GB, 7,200 RPM 3.5-type: 5874.22 GB, 7,200 RPM 3.5-type: 9790.36 GB, 7,200 RPM | |
FMD drive tray |
Flash module drive: 1759.21 GB, 3518.43 GB, 7036.87 GB, 14073.74 GB | |
Maximum number of drives that can be mounted | CBSS |
24 drives |
CBSL |
12 drives | |
SFF drive tray (VSP Gx00 models only) |
24 drives | |
LFF drive tray (VSP Gx00 models only) |
12 drives | |
FMD drive tray |
12 drives | |
Dense intermix drive tray (VSP Gx00 models only) |
60 drives | |
Maximum number of spare drives |
16 |
Item |
Component |
Specification |
Interface type |
Fibre Channel optical |
8-Gbps, 16-Gbps, 32-Gbps |
iSCSI optical |
10-Gbps | |
Copper iSCSI |
10-Gbps | |
Data transfer speed (maximum speed for transfer to host) |
Fibre Channel optical |
800-Mbps (Fibre Channel) |
Fibre Channel optical |
1600-Mbps (Fibre Channel) | |
Fibre Channel optical |
3200-Mbps (Fibre Channel) | |
iSCSI optical |
10-Gbps (iSCSI optical) | |
Copper iSCSI | 10-Gbps (copper iSCSI) | |
Number of ports |
8-Gbps Fibre Channel optical |
16 |
16-Gbps Fibre Channel optical (2-port) |
8 | |
16-Gbps Fibre Channel optical (4-port) |
16 | |
32-Gbps Fibre Channel optical |
16 | |
10-Gbps optical iSCSI |
8 | |
10-Gbps copper iSCSI |
8 | |
Transferred block size |
512 bytes | |
Maximum number of hosts using a Fibre Channel switch |
255 | |
Maximum number of hosts using a network switch |
255 |
Storage system intake temperature | CBSS | CBSL |
Up to 75.2º F (24º C) | 5 years | 5 years |
Up to 86º F (30º C) | 5 years | 4 years |
Up to 93.2º (34º C) | 4 years | 3 years |
Up to 104º (40º C) | 3 years | 2 years |
D: Data drive, P: Parity drive.
Although the storage system with a configuration of RAID 1, RAID 5, or RAID 6 provides data reliability enhanced by redundancy, there is a chance that user data could be lost due to an unexpected host, storage system hardware, or software failure. Therefore, users are requested to back up all data.
Item |
Drive tray |
RAID Level |
SAS, SAS 7.2k, flash drives mounted |
RAID 1 |
2D+2D, 4D+4D |
RAID 5 |
3D+1P, 4D+1P, 6D+1P, 7D+1P |
RAID 6 |
6D+2P, 12D+2P, 14D+2P |
Item |
Specification |
Maximum number of parity groups |
88 |
Maximum volume size |
3 TB (or 4 TB when using the LDEVs of other storage systems) |
Maximum volumes/host groups and iSCSI targets |
2,048 |
Maximum volumes/parity groups |
2,048 |
Item |
Component |
Specifications |
Shared memory |
Flash memory |
32 MB |
L3 cache memory |
4 MB | |
SDRAM |
1 GB | |
Data assurance method |
Data bus |
Parity |
Cache memory |
ECC (1 bit for correction, 2 bits for detection) | |
Drive |
Data assurance code |
Item |
Component |
Specifications |
Start-up time (min)1 | Controller |
Standard: 5 to 8 |
Drive trays |
Standard: 5 to 8 | |
Chassis size | Controller |
WxDxH: 19 x 32 x 3.5 inches (483 x 813 x 88 mm) |
SFF drive tray (VSP Gx00 models only) |
WxDxH: 19 x 22.2 x 3.5 inches (483 x 565 x 88.2 mm) | |
LFF drive tray (VSP Gx00 models only) |
WxDxH: 19 x 22.2 x 3.5 inches (483 x 565 x 88.2 mm) | |
FMD drive tray |
WxDxH: 19 x 30 x 3.4 inches (483 x 762 x 87 mm) | |
Dense intermix drive tray (VSP Gx00 models only) |
WxDxH: 19 x 40.5 x 7 inches (482 x 1029 x 176 mm) | |
Mass (approximate)2 | CBSS |
97 lbs (44 kg) |
CBSL |
101.4 lbs (46 kg) | |
SFF drive tray (VSP Gx00 models only) |
51 lbs (23 kg) | |
LFF drive tray (VSP Gx00 models only) |
59.5 lbs (27 kg) | |
FMD drive tray |
84 lbs (38 kg) | |
Dense intermix drive tray (VSP Gx00 models only) |
198 lbs (90 kg) | |
Required height | CBSS, CBSL | 2 |
SFF drive tray (VSP Gx00 models only) | 2 | |
LFF drive tray (VSP Gx00 models only) | 2 | |
FMD drive tray | 2 | |
Dense intermix drive tray (VSP Gx00 models only) | 4 | |
Notes
|
Item |
Specifications |
Capacity (GB) |
64 GB |
Control method |
Read LRU, Write after |
Battery backup |
Provided |
Backup duration |
Unrestricted (saving to a nonvolatile memory) |
Data in the cache memory is preserved against power failures. If a power outage occurs, data in cache memory is written to drives.
When the storage system enters Cache Backup mode, the amber WARNING LED goes on to when the system starts. This warning indicates that the battery charge has dropped significantly and the remaining battery capacity is not sufficient; the storage system will continue operating with the Write Cache function disabled.
When the battery is charged, the warning indication disappears, and the storage system continues the operation in the Write Cache function.
The warning indication disappears within six hours. Even when the warning is shown, normal operation is assured in Write-Through. Read and write performance is lowered because the Write Cache function is disabled.
If the storage system is not charged for more than six months, the battery can become overcharged and sustain unrecoverable damage. To avoid this situation, charge the battery more than 3 hours every six months.
Item |
Specifications |
Insulation withstand voltage |
AC 1,500 V (100 mA, 1 min) |
Insulation resistance |
DC 500 V, 10 M Ω or more |
VSP G200 mechanical specifications (DC power supply model)
Controller
1 CBSSD
1 CBSLD
Drive trays
1 SFF drive tray (DBSD)
1 LFF drive tray (DBLD)
Item |
Component |
Specification |
Drive size (WxDxH) | CBSSD, SFF drive tray |
2.5-type: 3.21 x 8.10 x 0.74 inches (81.6 x 205.7 x 18.7 mm) |
CBSLD, LFF drive tray |
3.5-type: 4 x 5.78 x 1.02 inches (101.6 x 147.0 x 26.1 mm) | |
Data capacity (GB) | CBSSD, SFF drive tray |
2.5-type: 196.92, 288.20, 393.85, 576.39, 1152.79, 1729.29, 1890.46 |
CBSLD, LFF drive tray |
3.5-type: 393.85, 1152.79, 1729.29, 3916.14, 5874.22, 9790.36 | |
Rotational speed (min-1) | CBSSD, SFF drive tray |
Flash drive, 2.5-type: 196.92 GB, 393.85 GB 2.5-type: 288.20 GB, 15,000 RPM 2.5-type: 576.39 GB, 10,000 or 15,000 RPM 2.5-type: 1152.79 GB, 10,000 RPM 2.5-type: 1729.29 GB, 10,000 RPM |
CBSLD, LFF drive tray |
Flash drive, 3.5-type: 393.85 GB 3.5-type: 1152.79 GB, 10,000 RPM 3.5-type: 1729.29 GB, 10,000 RPM 3.5-type: 3916.14 GB, 7,200 RPM 3.5-type: 5874.22 GB, 7,200 RPM 3.5-type: 9790.36 GB, 7,200 RPM | |
Maximum number of drives that can be mounted | CBSSD, SFF drive tray |
24 drives |
CBSLD, LFF drive tray |
12 drives | |
Maximum number of spare drives |
16 |
Storage system intake temperature | CBSS | CBSL |
Up to 75.2º F (24º C) | 5 years | 5 years |
Up to 86º F (30º C) | 5 years | 4 years |
Up to 93.2º (34º C) | 4 years | 3 years |
Up to 104º (40º C) | 3 years | 2 years |
Item |
Component |
Specification |
Interface type |
Fibre Channel optical |
8-Gbps, 16-Gbps, 32-Gbps |
iSCSI optical |
10-Gbps | |
Copper iSCSI |
10-Gbps | |
Data transfer speed (maximum speed for transfer to host) |
Fibre Channel optical |
800-Mbps (Fibre Channel) |
Fibre Channel optical |
1600-Mbps (Fibre Channel) | |
Fibre Channel optical |
3200-Mbps (Fibre Channel) | |
iSCSI optical |
10-Gbps (iSCSI optical) | |
Copper iSCSI | 10 Gbps (copper iSCSI) | |
Number of ports |
8-Gbps Fibre Channel optical |
16 |
16-Gbps Fibre Channel optical (2-port) |
8 | |
16-Gbps Fibre Channel optical (4-port) |
16 | |
32-Gbps Fibre Channel optical |
16 | |
10-Gbps optical iSCSI |
8 | |
10 Gbps copper iSCSI |
8 | |
Transferred block size |
512 bytes | |
Maximum number of hosts using a Fibre Channel switch |
255 | |
Maximum number of hosts using a network switch |
255 |
D: Data drive, P: Parity drive.
Although the storage system with a configuration of RAID 1, RAID 5, or RAID 6 provides data reliability enhanced by redundancy, there is a chance that user data could be lost due to an unexpected host, storage system hardware, or software failure. Therefore, users are requested to back up all data.
Item |
Drive tray |
RAID Level |
SAS, SAS 7.2k, flash drives mounted |
RAID 1 |
2D+2D, 4D+4D |
RAID 5 |
3D+1P, 4D+1P, 6D+1P, 7D+1P |
RAID 6 |
6D+2P, 12D+2P, 14D+2P |
Item |
Specification |
Maximum number of parity groups |
88 |
Maximum volume size |
3 TB (or 4 TB when using the LDEVs of other storage systems) |
Maximum volumes/host groups and iSCSI targets |
2,048 |
Maximum volumes/parity groups |
2,048 |
Item |
Component |
Specifications |
Shared memory |
Flash memory |
32 MB |
L3 cache memory |
4 MB | |
SDRAM |
1 GB | |
Data assurance method |
Data bus |
Parity |
Cache memory |
ECC (1 bit for correction, 2 bits for detection) | |
Drive |
Data assurance code |
Item |
Component |
Specifications |
Start-up time (min)1 | Controller |
Standard: 5 to 8 |
Drive trays |
Standard: 5 to 8 | |
Chassis size | Controller |
WxDxH: 19 x 32 x 3.5 inches (483 x 813 x 88 mm) |
SFF drive tray (VSP Gx00 models only) |
WxDxH: 19 x 22.2 x 3.5 inches (483 x 565 x 88.2 mm) | |
LFF drive tray (VSP Gx00 models only) |
WxDxH: 19 x 22.2 x 3.5 inches (483 x 565 x 88.2 mm) | |
Mass (approximate)2 | CBSSD |
97 lbs (44 kg) |
CBSLD |
101.4 lbs (46 kg) | |
SFF drive tray (VSP Gx00 models only) |
51 lbs (23 kg) | |
LFF drive tray (VSP Gx00 models only) |
59.5 lbs (27 kg) | |
Required height | CBSSD, CBSLD | 2 |
SFF drive tray (VSP Gx00 models only) | 2 | |
LFF drive tray (VSP Gx00 models only) | 2 | |
Notes
|
Item |
Specifications |
Capacity (GB) |
64 GB |
Control method |
Read LRU, Write after |
Battery backup |
Provided |
Backup duration |
Unrestricted (saving to a nonvolatile memory) |
Data in the cache memory is preserved against power failures. If a power outage occurs, data in cache memory is written to drives.
When the storage system enters Cache Backup mode, the amber WARNING LED goes on to when the system starts. This warning indicates that the battery charge has dropped significantly and the remaining battery capacity is not sufficient; the storage system will continue operating with the Write Cache function disabled.
When the battery is charged, the warning indication disappears, and the storage system continues the operation in the Write Cache function.
The warning indication disappears within six hours. Even when the warning is shown, normal operation is assured in Write-Through. Read and write performance is lowered because the Write Cache function is disabled.
If the storage system is not charged for more than six months, the battery can become overcharged and sustain unrecoverable damage. To avoid this situation, charge the battery more than 3 hours every six months.
Item |
Specifications |
Insulation withstand voltage |
AC 1,500 V (100 mA, 1 min) |
Insulation resistance |
DC 500 V, 10 M Ω or more |
VSP G400 or VSP F400 and VSP G600 or VSP F600 mechanical specifications
Controller
1 CBLM
Drive tray
1 SFF drive tray (VSP Gx00 models only)
1 LFF drive tray (VSP Gx00 models only)
1 FMD drive tray
1 Dense intermix drive tray (VSP Gx00 models only)
Item | Description |
NAS module |
Optional component for block and file storage configuration |
Drive size
Item | Specification |
2.5-inch drive (SFF) (VSP Gx00 models only) | 3.21 x 8.10 x 0.74 inches (81.6 x 205.7 x 18.7 mm) |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) | 4 x 5.78 x 1.02 inches (101.6 x 147.0 x 26.1 mm) |
Flash Module Drive (flash module drive tray) | 5.74 x 14.44 x 0.78 inches (146 x 366.8 x 19.8 mm) |
Data capacity (GB)
2.5-inch drive (SFF) (VSP Gx00 models only) | 196.92, 288.20, 393.85, 576.39, 1152.79, 1729.29, 1890.46 |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) | 393.85, 1152.79, 1729.29, 3916.14, 5874.22, 9790.36 |
Flash Module Drive (flash module drive tray) | 1759.21, 3518.43 , 7036.87, 14073.74 |
Rotational speed (min-1)
2.5-inch drive (SFF) (VSP Gx00 models only) |
196.92/393.85 GB 2288.20 GB: 15,000 RPM 576.39 GB: 10,000 or 15,000 RPM 1152.79 GB: 10,000 RPM 1729.29 GB: 10,000 RPM |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) |
393.85 GB: Flash drive 1152.79 GB: 10,000 RPM 1729.29 GB: 10,000 RPM 3916.14 GB: 7,200 RPM 5874.22 GB: 7,200 RPM 9790.36 GB: 7,200 RPM |
Maximum mountable quantity
Mixing SFF, LFF, FMD, and dense intermix drive trays might affect the maximum number of drives that can be mounted.
SFF (VSP Gx00 models only) | 24 |
LFF (VSP Gx00 models only) | 12 |
Flash module drive (flash module drive tray) (VSP Gx00 models only) | 12 |
Dense intermix drive tray (VSP Gx00 models only) | 60 |
Maximum number of flash module drives (VSP Fx00 models) | VSP F400: 8 +1 spare drive
VSP F600 16 + 1 spare drive |
Battery specifications
Storage system intake temperature | CBLMCBLH |
Up to 75.2º F (24º C) | 5 years |
Up to 86º F (30º C) | 5 years |
Up to 93.2º (34º C) | 4 years |
Up to 104º (40º C) | 3 years |
Host interface
Item |
Component |
Specification |
Interface type |
Fibre Channel optical |
8-Gbps, 16-Gbps, 32-Gbps |
iSCSI optical |
10-Gbps | |
iSCSI copper |
10-Gbps | |
NAS module |
10-Gbps (Fibre Channel optical) | |
Data transfer speed (maximum speed for transfer to host) |
Fibre Channel optical |
800-Mbps (Fibre Channel) |
1600-Mbps (Fibre Channel) | ||
3200-Mbps (Fibre Channel) | ||
iSCSI optical |
10-Gbps (iSCSI optical) | |
iSCSI copper |
10-Gbps (iSCSI copper) | |
NAS module (Fibre Channel) |
1000 Mbs | |
Number of ports |
8-Gbps Fibre Channel optical | 64 |
16-Gbps Fibre Channel optical (2-port) | 32 | |
16-Gbps Fibre Channel optical (4-port) | 64 | |
32-Gbps Fibre Channel optical | 64 | |
10-Gbps optical iSCSI | 32 | |
10-Gbps copper iSCSI | 32 | |
Number of ports (NAS Module not installed) |
8-Gbps Fibre Channel optical |
64 56 |
16-Gbps Fibre Channel optical (2-port) |
32 28 | |
16-Gbps Fibre Channel optical (4-port) |
64 56 | |
32-Gbps Fibre Channel optical |
64 56 | |
10-Gbps optical iSCSI |
32 28 | |
10-Gbps copper iSCSI |
32 28 | |
Number of ports (NAS Module installed) |
8-Gbps Fibre Channel optical |
24 |
16-Gbps Fibre Channel optical (2-port) |
12 | |
16-Gbps Fibre Channel optical (4-port) |
24 | |
32-Gbps Fibre Channel optical |
24 | |
10-Gbps optical iSCSI |
12 | |
10-Gbps copper iSCSI |
12 | |
10-Gbps Fibre Channel optical |
12 | |
Transferred block size |
512 bytes | |
Maximum number of hosts using a Fibre Channel switch |
255 | |
Maximum number of hosts using a network switch |
255 |
D: Data drive, P: Parity drive.
Although the storage system with a configuration of RAID 1, RAID 5, or RAID 6 provides data reliability enhanced by redundancy, there is a chance that user data could be lost due to an unexpected host, storage system hardware, or software failure. Therefore, users are requested to back up all data.
RAID Level |
SAS, SAS 7.2k, flash drives mounted |
RAID 1 |
2D+2D, 4D+4D |
RAID 5 |
3D+1P, 4D+1P, 6D+1P, 7D+1P |
RAID 6 |
6D+2P, 12D+2P, 14D+2P |
Item |
Specification |
Maximum number of RAID groups |
VSP G400 or VSP F400:160 VSP G600 or VSP F600:240 |
Maximum volume size |
3 TB (or 4 TB when using the LDEVs of other storage systems) |
Maximum volumes/host groups and iSCSI targets |
2048 |
Maximum number of volumes per RAID group |
2048 |
Shared memory and data assurance
Item | Specification |
Flash memory | 32 MB |
L3 Cache memory | 4 MB |
SDRAM | 1 GB |
Data bus | Parity |
Cache memory | ECC (1 bit for correction, 2 bits for detection) |
Drive | Data assurance code |
Start-up time
Item |
Standard: 5-to-8 minutes.
The start-up time may be longer in proportion to the number of drive trays connected. With a maximum configuration 1 controller tray and 19 drive trays, start-up time is approximately 8 minutes. |
Chassis size
Component |
Specification (WxDxH) |
CBLM | 19.01 x 35.10 x 6.86 inches (483 x 891.7 x 174.3 mm) |
SFF/LFF (VSP Gx00 models only) | 18.97 x 22.24 x 3.47 inches (482 x 565 x 88.2 mm) |
DBF | 19.01 x 30 x 3.42 inches (483 x 762 x 87 mm) |
Dense intermix drive tray (VSP Gx00 models only) | 18.97 x 40.51 x 6.92 inches (482 x 1,029 x 176 mm)
(includes the depth of the cable-management arms) |
Mass (value of maximum configuration when all controllers and drives are mounted)
Component |
Specification |
CBLM | 187.39 pounds (85 kg) |
SFF (VSP Gx00 models only) | Approx 50.70 inches (23 kg) |
LFF (VSP Gx00 models only) | Approx 59.52 inches (27 kg) |
DBF | Approx. 83.77 pounds (38 kg) |
Dense intermix drive tray (VSP Gx00 models only) | Approx. 198.41 pounds (90 kg) |
Required height
Component |
Specification |
CBLM | 4 U |
SFF (VSP Gx00 models only) | 2 U |
LFF (VSP Gx00 models only) | 2 U |
DBF | 2 U |
Dense intermix drive tray (VSP Gx00 models only) | 4 U
If a drive is inserted into a slot of a dense intermix drive tray when the installed number of drives exceeds 240 slots per path, the drive is blocked. |
Item |
Specification |
Capacity (GB) |
VSP G400: 128 VSP G600: 256 VSP F400: 128 VSP F600: 256 |
NAS module Cache Capacity |
DDR3 DIMM 8GB x 12 [Slot] Note:
|
Control method |
Read LRU, Write after |
Battery backup |
Provided |
Backup duration |
Unrestricted (saving to a nonvolatile memory) |
Data in the cache memory is preserved against power failures. If a power outage occurs, data in cache memory is written to drives.
When the storage system enters Cache Backup mode, the amber WARNING LED goes on to when the system starts. This warning indicates that the battery charge has dropped significantly and the remaining battery capacity is not sufficient; the storage system will continue operating with the Write Cache function disabled.
When the battery is charged, the warning indication disappears, and the storage system continues the operation in the Write Cache function.
The warning indication disappears within six hours. Even when the warning is shown, normal operation is assured in Write-Through. Read and write performance is lowered because the Write Cache function is disabled.
If the storage system is not charged for more than six months, the battery can become overcharged and sustain unrecoverable damage. To avoid this situation, charge the battery more than 3 hours every six months.
Item |
Specification |
Insulation withstand voltage |
AC 1,500 V (100 mA, 1 min) |
Insulation resistance |
DC 500 V, 10 M Ω or more |
VSP G800VSP F800 mechanical specifications
Controller
1 CBLH
Drive tray
1 SFF drive tray (VSP Gx00 models only)
1 LFF drive tray (VSP Gx00 models only)
1 FMD drive tray
1 Dense intermix drive tray (VSP Gx00 models only)
Item | Description |
NAS module |
Optional component for block and file storage configuration |
Drive size
Item | Specification |
2.5-inch drive (SFF) (VSP Gx00 models only) | 3.21 x 8.10 x 0.74 inches (81.6 x 205.7 x 18.7 mm) |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) | 4 x 5.78 x 1.02 inches (101.6 x 147.0 x 26.1 mm) |
Flash Module Drive (flash module drive tray) | 5.74 x 14.44 x 0.78 inches (146 x 366.8 x 19.8 mm) |
Data capacity (GB)
2.5-inch drive (SFF) (VSP Gx00 models only) | 196.92, 288.20, 393.85, 576.39, 1152.79, 1729.29, 1890.46 |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) | 393.85, 1152.79, 1729.29, 3916.14, 5874.22, 9790.36 |
Flash Module Drive (flash module drive tray) | 1759.21, 3518.43 , 7036.87, 14073.74 |
Rotational speed (min-1)
2.5-inch drive (SFF) (VSP Gx00 models only) |
196.92/393.85 G bytes 2288.20 GB: 15,000 RPM 576.39 GB: 10,000 or 15,000 RPM 1152.79 GB: 10,000 RPM 1729.29 GB: 10,000 RPM |
3.5-inch drive (LFF and dense intermix drive tray) (VSP Gx00 models only) |
393.85 G bytes: Flash drive 1152.79 G bytes: 10,000 RPM 1729.29 G bytes: 10,000 RPM 3916.14 G bytes: 7,200 RPM 5874.22 G bytes: 7,200 RPM 9790.36 G bytes: 7,200 RPM |
Maximum mountable quantity
Mixing SFF, LFF, FMD, and dense intermix drive trays might affect the maximum number of drives that can be mounted.
SFF (VSP Gx00 models only) | 24 |
LFF (VSP Gx00 models only) | 12 |
Dense intermix drive tray (VSP Gx00 models only) | 60 |
Flash module drive (flash module drive tray) (VSP Gx00 models only) | 12 |
Maximum number of spare drives (VSP Gx00 models only) | 64 |
Maximum number of flash module drives (VSP Fx00 models) | 40 |
Maximum number of spare drives (VSP Fx00 models) | 2 |
Battery specifications
Storage system intake temperature | CBLMCBLH |
Up to 75.2º F (24º C) | 5 years |
Up to 86º F (30º C) | 5 years |
Up to 93.2º (34º C) | 4 years |
Up to 104º (40º C) | 3 years |
Host interface
Item |
Component |
Specification |
Interface type |
Fibre Channel optical |
8-Gbps, 16-Gbps, 32-Gbps |
iSCSI optical |
10-Gbps | |
iSCSI (Copper) |
10-Gbps | |
NAS module |
10 Gbps (Fibre Channel optical) | |
Data transfer speed (maximum speed for transfer to host) |
Fibre Channel optical |
800-Mbps (Fibre Channel) |
1600-Mbps (Fibre Channel) | ||
3200-Mbps (Fibre Channel) | ||
iSCSI optical |
10-Gbps (iSCSI optical) | |
iSCSI (Copper) |
10 Gbps (iSCSI copper) | |
NAS module (Fibre Channel) |
1000 Mbs | |
VSP G800 maximum number of ports |
8 Gbps Fibre Channel (optical) |
64 |
16 Gbps Fibre Channel (optical 2-port) |
32 | |
16 Gbps Fibre Channel (optical 4-port) |
64 | |
32 Gbps Fibre Channel (optical) |
64 | |
10 Gbps iSCSI optical) |
32 | |
10 Gbps iSCSI (copper) |
32 | |
VSP F800 maximum number of ports |
8 Gbps Fibre Channel (optical) |
48 |
16 Gbps Fibre Channel (optical) |
24 | |
32 Gbps Fibre Channel (optical) |
48 | |
10 Gbps iSCSI (optical) |
24 | |
10 Gbps iSCSI (copper) |
24 | |
Maximum number of ports (NAS module installed) |
8 Gbps Fibre Channel (optical) |
16 |
16 Gbps Fibre Channel (optical 2-port) |
8 | |
16 Gbps Fibre Channel (optical 4-port) |
16 | |
32 Gbps Fibre Channel (optical) |
16 | |
10 Gbps iSCSI (optical) |
8 | |
10 Gbps iSCSI (copper) |
8 | |
10 Gbps Fibre Channel (optical) |
12 | |
Maximum number of ports (NAS modules not installed) |
8 Gbps Fibre Channel (optical) |
80 |
16 Gbps Fibre Channel (optical 2-port) |
40 | |
16 Gbps Fibre Channel (optical 4-port) |
80 | |
32 Gbps Fibre Channel (optical) |
80 | |
10 Gbps iSCSI (optical) |
40 | |
10 Gbps iSCSI (copper) |
40 | |
Maximum number of ports (host port expansion chassis and NAS module installed) |
8 Gbps Fibre Channel (optical) |
32 |
16 Gbps Fibre Channel Optical (2-port) |
16 | |
16 Gbps Fibre Channel Optical (4-port) |
32 | |
32 Gbps Fibre Channel Optical (4-port) |
32 | |
10 Gbps iSCSI (optical) |
16 | |
10 Gbps iSCSI (copper) |
16 | |
10 Gbps Fibre Channel (optical) |
12 | |
Transferred block size |
512 bytes | |
Maximum number of hosts using a Fibre Channel switch |
255 | |
Maximum number of hosts using a network switch |
255 |
D: Data drive, P: Parity drive.
Although the storage system with a configuration of RAID 1, RAID 5, or RAID 6 provides data reliability enhanced by redundancy, there is a chance that user data could be lost due to an unexpected host, storage system hardware, or software failure. Therefore, users are requested to back up all data.
RAID Level |
SAS, SAS 7.2k, flash drives mounted |
RAID 1 |
2D+2D, 4D+4D |
RAID 5 |
3D+1P, 4D+1P, 6D+1P, 7D+1P |
RAID 6 |
6D+2P, 12D+2P, 14D+2P |
Item |
Specification |
Maximum number of RAID groups | 480 |
Maximum number of RAID groups | 480 |
Maximum volume size |
3 TB (or 4 TB when using the LDEVs of other storage systems) |
Maximum volumes/host groups and iSCSI targets |
2048 |
Maximum volumes/parity groups |
2048 |
Shared memory and data assurance
Item | Specification |
Flash memory | 32 M bytes |
L3 Cache memory | 4 M bytes |
SDRAM | 1 G bytes |
Data bus | Parity |
Cache memory | ECC (1 bit for correction, 2 bits for detection) |
Drive | Data assurance code |
Start-up time
Item |
Standard: 5-to-10 minutes.
The start-up time may be longer in proportion to the number of drive trays connected. With a maximum configuration 1 controller tray and 19 drive trays, start-up time is approximately 10 minutes. |
Chassis size
Component |
Specification (WxDxH) |
CBLH | 19.01 x 35.10 x 6.86 inches (483 x 891.7 x 174.3 mm) |
SFF/LFF (VSP Gx00 models only) | 18.97 x 22.24 x 3.47 inches (482 x 565 x 88.2 mm) |
DBF | 19.01 x 30 x 3.42 inches (483 x 762 x 87 mm) |
Dense intermix drive tray (VSP Gx00 models only) | 18.97 x 40.51 x 6.92 inches (482 x 1,029 x 176 mm)
(includes the depth of the cable-management arms) |
Mass (value of maximum configuration when all controllers and drives are mounted)
Component |
Specification |
CBLH | 187.39 pounds (85 kg) |
SFF (VSP Gx00 models only) | Approx 50.70 inches (23 kg) |
LFF (VSP Gx00 models only) | Approx 59.52 inches (27 kg) |
DBF | Approx. 83.77 pounds (38 kg) |
Dense intermix drive tray (VSP Gx00 models only) | Approx. 198.41 pounds (90 kg) |
Required height
Component |
Specification |
CBLH | 4 U |
SFF (VSP Gx00 models only) | 2 U |
LFF (VSP Gx00 models only) | 2 U |
DBF | 2 U |
Dense intermix drive tray (VSP Gx00 models only) | 4 U
If a drive is inserted into a slot of a dense intermix drive tray when the installed number of drives exceeds 240 slots per path, the drive is blocked. |
Item |
Specification |
Capacity (GB) |
VSP G800: 512 VSP F800: 512 |
NAS module Cache Capacity |
DDR3 DIMM 8GB x 12 [Slot]
Note
|
Control method |
Read LRU, Write after |
Battery backup |
Provided |
Backup duration |
Unrestricted (saving to a nonvolatile memory) |
Data in the cache memory is preserved against power failures. If a power outage occurs, data in cache memory is written to drives.
When the storage system enters Cache Backup mode, the amber WARNING LED goes on to when the system starts. This warning indicates that the battery charge has dropped significantly and the remaining battery capacity is not sufficient; the storage system will continue operating with the Write Cache function disabled.
When the battery is charged, the warning indication disappears, and the storage system continues the operation in the Write Cache function.
The warning indication disappears within six hours. Even when the warning is shown, normal operation is assured in Write-Through. Read and write performance is lowered because the Write Cache function is disabled.
If the storage system is not charged for more than six months, the battery can become overcharged and sustain unrecoverable damage. To avoid this situation, charge the battery more than 3 hours every six months.
Item |
Specification |
Insulation withstand voltage |
AC 1,500 V (100 mA, 1 min) |
Insulation resistance |
DC 500 V, 10 M Ω or more |
Electrical specifications for VSP G200VSP G400, G600VSP G800VSP F400, F600VSP F800
The electrical specifications are described for the storage systems.
Electrical specifications
Item |
Controller |
Drive tray |
Input voltage (operable voltage range) (V) |
AC 100-120/200-240 +6%/-11% |
SFF, LFF, FMD, and dense intermix drive tray: AC 200-240 +6%/-11% |
Input voltage (operable voltage range) (V) |
AC 200-240 +6%/-11% |
SFF, LFF, FMD, and dense intermix drive tray: AC 200-240 +6%/-11% |
Frequency (Hz) | 50/60 ±1 | |
Number of phases, cabling | Single-phase with protective grounding | |
Steady-state current 100V/200V1, 2 |
CBSS: 4.0x2/2.0x2 CBSL: 4.0x2/2.0x2 CBLM: 4.0x2 CBLH: 4.0x2 |
SFF drive tray: 2.4x2/1.2x2 LFF drive tray: 1.9x2/1.0x2 FMD drive tray: 2.6x2/1.3x2 Dense intermix drive tray: -/3.0x2 |
Current rating of breaker/fuse (A) | 16.0 (each electrical) | |
Heat value (normal) (kJ/h) |
CBSS: 1800 or less CBSL 1550 or less CBLM: 2160 or less 2810 or less |
SFF drive tray: 1120 or less LFF drive tray: 940 or less FMD drive tray: 1300/1520 or less FMD drive tray: 1520 or less FMD drive tray: 1520 or less Dense intermix drive tray: 3460 or less |
Steady-state power (VA/W)3 |
CBSS: 800/760 or less CBSL: 800/760 or less CBLM: 1600/1560 or less CBLH: 1600/1560 or less |
SFF drive tray: 480/460 or less LFF drive tray: 380/350 or less FMD drive tray: 520/490 or less Dense intermix drive tray: 1200/1160 or less |
Power consumption (VA/W) |
CBSS: 520/500 or less CBSL: 450/430 or less CBLM: 640/600 or less CBLH: 840/780 or less |
SFF drive tray: 320/310 or less LFF drive tray: 280/260 or less FMD drive tray: 440/420 or less Dense intermix drive tray: 1000/960 or less |
Notes:
|
VSP G200 electrical specifications (DC power supply)
Item |
CBSSD |
CBSLD |
DBSD |
DBLD |
Rated input voltage (v) | DC -60 to -48 | |||
Input voltage fluctuation (v) | DC -72 to -40 | |||
Input voltage instant fluctuation (v) | DC -75 to -36 | |||
Inrush current (v) | 35 (Ta = 25°C, in the range of rated input voltage, except when voltage fluctuates) | |||
Input shape | Connection by connector. Connect the terminal by the dedicated cable with terminal. Connector: Positronic Industries Inc., PCS Series | |||
Heat value (kJ/h) | 1800 | 1550 | 1120 | 940 |
Steady-state power (W) | 760 | 760 | 460 | 350 |
Power consumption (W) | 500 | 430 | 310 | 260 |
Input current (A) | 15.9 | 15.9 | 9.6 | 7.3 |
UPS | No connection | |||
Remote adapter | No connection |
Environmental specifications for VSP G200VSP G400, G600VSP G800VSP F400, F600VSP F800
The environmental specifications are described for the storage systems.
Environmental specifications
- DB60 dense drive tray
- Hitachi provided service processor (SVP) server
- First-generation FMDs (non-DC2 FMDs)
State |
Controller |
SFF, LFF drive trays |
Dense intermix drive tray | |
Operating | 50°F to 104°F (10°C to 40°C) | 50°F to 104°F (10°C to 40°C) | 50°F to 95°F (10°C to 35°C) | |
Non-operating | 14°F to 122°F (-10°C to 50°C) | 14°F to 122°F (-10°C to 50°C) | 14°F to 122°F (-10°C to 50°C) | |
Transport, storage | -22°F to 140°F (-30°C to 60°C) | -22°F to 140°F (-30°C to 60°C) | -22°F to 140°F (-30°C to 60°C) | |
Temperature change rate (°C/h) | 10 or less |
State |
Controller |
FMD drive trays | ||
Operating | 50°F to 104°F (10°C to 40°C) | DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed: 50°F to 95°F (10°C to 35°C) | ||
Operating | 50°F to 104°F (10°C to 40°C) | DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed: 50°F to 104°F (10°C to 40°C) | ||
Non-operating | 14°F to 122°F (-10°C to 50°C) | 14°F to 95°F (-10°C to 35°C) | ||
Transport, storage | -22°F to 140°F (-30°C to 60°C) | -22°F to 122°F (-30°C to 50°C) | ||
Temperature change rate (°C/h) | 10 or less |
State |
Percentage |
Operating | 8 to 80 |
Non-operating | 8 to 90 |
Transport, storage (%) | 5 to 95 |
Maximum wet bulb temperature (°C) | 29 (non-condensing) |
State |
m/s2 |
Operating | 2.5 or less
Within 5 seconds (resonance point: 10 Hz or less) |
Non-operating | 5.0 or less at 5 Hz to 300 Hz (no damage to product)
9.8 (1.0 G) Within 5 seconds (resonance point: 10 Hz or less) |
Transport (packed) | 5.0 or less |
State |
m/s2 |
Operating | 20 or less
(10 ms, half sine wave) |
Non-operating | 50 or less
(10 ms, half sine wave) |
Transport (packed) | 80 or less |
State |
Controller |
FMD drive | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) 900 (Environmental temperature: 10°C to 40°C) |
3,000 (Environmental temperature 10°C to 32°C) OR 900 (Environmental temperature: 10°C to 35°C) when DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed. | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) 900 (Environmental temperature: 10°C to 40°C) |
3,000 (Environmental temperature: 10°C to 32°C) OR 900 (Environmental temperature: 10°C to 40°C) when DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is installed. | ||
Non-operating (m) | -60 to 12,000 | N/A |
State |
Controller |
SFF and LFF drives |
Dense intermix drive tray | ||
Operating (m) |
3,000 (Environmental temperature: 10°C to 32°C) |
3,000 (Environmental temperature: 10°C to 32°C) |
3,000 (Environmental temperature: 10°C to 28°C) 1,000 (Environmental temperature: 10°C to 35°C) | ||
900 (Environmental temperature: 10°C to 40°C) |
900 (Environmental temperature: 10°C to 40°C) | ||||
Non-operating (m) | N/A |
Avoid areas exposed to corrosive gas and salty air.
State |
Controller |
SFF, LFF |
Dense intermix drive tray | |
Operating | 60 dB (Environmental temperature 32°C or less)1 | 60 dB (Environmental temperature 32°C or less)1 | 71 dB (Environmental temperature 32°C or less)1, 2, 3, 4 | |
Non-operating | 55 dB | 55 dB | 71 dB (Environmental temperature 32°C or less)1, 2, 3, 4 | |
Notes:
|
State |
Controller |
FMD | ||
Operating | 60 dB (Environmental temperature 32°C or less)1 | 60 dB (Environmental temperature 32°C or less)1,
2,
3
(When accessing the dense intermix drive tray, do not work for long times at the rear of the rack.) | ||
Non-operating | 55 dB (Environmental temperature 32°C or less)1, 2, 3, 4 55 dB | |||
Notes:
|
VSP G200 environmental specifications (DC power supply)
Item |
CBSSD/CBSLD/DBSD/DBLD |
Notes | ||
Temperature | Operating |
41°F to 104°F (5°C to 40°C) | ||
Non-operating |
23°F to 131°F (-5 to 55°C) in 16 hours | |||
Transport/storage) |
-22°F to 140°F (-30°C to 60°C) | |||
Humidity | Operating |
5% to 85% (non-condensing) | ||
Transportation/storage |
5% to 95% (non-condensing) | |||
Vibration | Operating (m/s2) |
2.5 or less (5 to 300 Hz) |
Within 5 seconds (Resonance point:10 Hz or less) | |
Non-operating (m/s2) |
5.0 or less (5 to 300 Hz): No critical damage for product. 9.8 (1.0 G) Adopt fall-prevention safety measures. | |||
Transport (packed) (m/s2) |
5.0 or less | |||
Impact | Operating (m/s2) |
20 or less |
10 ms, half sine wave | |
Non-operating (m/s2) |
50 or less | |||
Transport (packed) (m/s2) |
80 or less | |||
Angle at which the storage system turns over |
15° or less |
To be measured when installed on leveling bolts. | ||
Altitude | Operating (m) |
-60 to 1,800 above sea level Environmental temperature: 41°F to 104°F (5°C to 40°C) -1,800 to 4,000 above sea level Environmental temperature: 41°F to 86°F (5°C to 30°C) | ||
Atmosphere |
No corrosive gas and salty air must be found. | |||
Acoustic Noise | Operating |
60 dB Environmental temperature: 89.6°F (32°C) or less The system's internal temperature controls the rotating speed of the fan. Therefore, this standard value might be exceeded if the maximum load continues under high-temperature environment or if a system failure occurs. |
Measured at the position 1.5 meter away from the storage system, at a height of 1.5 meters. | |
Standby |
55 dB |
iSCSI specifications
Item |
Specification |
Comments |
iSCSI target function | Supported | N/A |
iSCSI target function | Supported | TrueCopy® only |
iSCSI ports | 2 per interface board |
VSP Gx00 models: Maximum 32 per iSCSI system VSP Fx00 models: Maximum 24 per iSCSI system |
Connection methods | Direct and switch connections | |
Host connections | 255 (maximum per iSCSI port) | With Linux software initiator, the maximum number decreases. |
Path failover | HDLM1 | Supports Microsoft MPIO (Multi Path I/O) |
Link | 10 Gbps SFP+ | N/A |
Transfer speed | 10 Gbps | N/A |
Connector type | LC | N/A |
Cable | Optical OM3, OM2 MMF cable | N/A |
Network switch | L2 or L3 switch | Should comply with IEEE802.3ae |
Switch cascading | Maximum: 5 switches or fewer | Minimum number of cascading switches is recommended. |
MAC address | Per port (fixed value) | Factory setting: World Wide Unique value. Cannot be changed. |
Maximum transfer unit (MTU) | 1,500, 4,500, 9,000 bytes (Ethernet frame) | Jumbo frame, MTU size greater than 1500 |
Link aggregation | Not supported | N/A |
Tagged VLAN | Supported | N/A |
IPv4 | Supported | N/A |
IPv6 | Supported |
Note the following precautions:
|
Subnet mask | Supported | N/A |
Gateway address | Supported | N/A |
DHCP | N/A | N/A |
DNS | N/A | N/A |
Ping (ICMP ECHO) Transmit, Receive | Supported | N/A |
IPsec2 | N/A | N/A |
TCP port number | 3260 | Changeable among 1 to 65,535. Observe the following if changing values:
|
iSCSI name | Both iqn3 and eui4 types are supported | The unique iqn value is automatically set when a target is made. iSCSI name is configurable. |
Error recovery level | 0 (zero) | Error recovery by retrying from host. Does not support Level 1 and Level 2. |
Header digest | Supported | Detects header error or data error with iSCSI communication. The storage system follows the host's digest setting. If digest is enabled, the performance degrades. The amount of the degradation depends on factors such as host performance of host and transaction pattern. |
Data digest | Supported | |
Maximum iSCSI connections at one time | 255 per iSCSI port | N/A |
CHAP | Supported | Authentication: login request is sent properly from host to storage. CHAP is not supported during discovery session. |
Mutual (2-way) CHAP | Supported (not available if connected to Linux software initiator) | Authentication: login request is sent properly from host to storage. |
CHAP user registration | Max 512 users per iSCSI port | N/A |
iSNS | Supported | With iSNS (name service), a host can discover a target without knowing the target's IP address. |
Note:
|
iSCSI standards
The following standards apply to the management, maintenance, and iSCSI data ports. To configure this system, use switches that comply with the following standards:
- IEEE 802.1D STP
- IEEE 802.1w RSTP
- IEEE 802.3 CSMA/CD
- IEEE 802.3u Fast Ethernet
- IEEE 802.3z 1000 BASE-X
- IEEE 802.1Q Virtual LANs
- IEEE 802.3ad Dynamic LACP
- IEEE 802.3ae 10 Gigabit Ethernet
- RFC 768 UDP
- RFC 783 TFTP
- RFC 791 IP
- RFC 793 TCP
- RFC 1157 SNMP v1
- RFC 1231 MIB II
- RFC 1757 RMON
- RFC 1901 SNMPv2
Regulatory compliance
This equipment has been tested and certified for compliance with the following standards.
Standard |
Specification |
Product marking or logo |
Country regulation |
Electronic emission controls | FCC part 15 Subpart B:2013 | FCC | USA and Canada |
ICES-003 Issue 5:2012 | ICES-003 | USA and Canada | |
AS/NZS CISPR 22:2009+A1 | RCM | Australia and New Zealand | |
TP TC 020/2011 | EAC | Russia, Belarus, and Kazakhstan | |
CNS 13438 | BSMI | Taiwan | |
KN22 | KC | Korea | |
KN24 | KC | Korea | |
Electronic emission certifications | EN5522: 2010 | CE | EU |
EN5524: 2010 | CE | EU | |
EN61000-3.2:2006+A1+A2 | CE | EU | |
EN61000-3.3:2008 | CE | EU | |
Safety certifications | UL and CSA 60950-1:2007 | cTUVus | USA and Canada |
EN60950-1:2006+A1 | TUV | Germany | |
IEC60950-1:2005+A1 | N/A | All CB countries | |
IEC60950-1:2005+A1 | S-Mark | Argentina | |
TP TC 004/2011 | EAC | Russia | |
CNS 14336-1 | BSMI | Taiwan | |
EN60950-1:2006+A1 | CE | EU | |
Radio interference voluntary control | VCCI V-3/2013.04 | VCCI | Japan |
Standard |
Certification |
Country regulation |
Description |
Federal Information Processing Standards (FIPS) |
#2727 FIPS 140-2 Level 1, 2 Consolidated Validation Certificate http://csrc.nist.gov/groups/STM/cmvp/documents/140-1/1401val2016.htm |
USA and Canada |
Encryption back end module provides high-speed data at rest encryption. |
Physical SVP specifications
The following sections describe the specifications for the physical SVP.
Service processor hardware specifications
The following table lists the hardware specifications for the service processor (SVP) provided by Hitachi Vantara.
Item |
Specification |
Dimensions |
Height: 1.7 inches (43 mm) Width: 17.2 inches (437 mm) Depth: 14.5 inches (369 mm) Weight: 14 lbs (6.4 kg) |
Processor |
Celeron G1820 2.7-GHz 2M, 2C, 2T
|
Memory |
8-GB RAM DDR3 |
Hard drive |
2 TB |
Network interface card |
x4 ports (on-board NIC) + x1 IPMI (BMC) port |
Fans |
2 x 4-cm 4-pin PWM fans |
Operating system |
Windows Embedded Standard 7 |
Physical SVP environmental specifications
The following table lists the environmental specifications for the physical SVP supplied by Hitachi Vantara.
Item |
Specification |
Operating temperature |
41°F ~ 95°F (5°C ~ 35°C) |
Non-operating temperature range |
-40°F ~ 140°F (-40°C ~ 60°C) |
Operating relative humidity range |
8% ~ 90% (non-condensing) |
Non-operating relative humidity range |
5% - 95% (non-condensing) |
Physical SVP electrical specifications
The following table lists the electrical specifications for the physical SVP supplied by Hitachi Vantara.
Item |
Specification | |
Rated AC voltage |
100-240 V, 50-60 Hz, 4.2 - 1.8A | |
Power supply |
350-Watt AC power supply with PFC | |
AC voltage |
100-240 V, 50-60 Hz, 4.2 - 1.8 Amp | |
Power supply safety / EMC |
| |
MFT p-code |
Description |
Watts |
MBD-X10SLM+-LN4F-O |
Single-socket H3 (LGA 1150) / 32-GB DDR3 ECC 1600 MHz / 6x SATA / 4x GbE |
20 |
CSE-512F-350B |
Two 350 W 3.5-inch internal drive bays |
26.4 |
CM8064601483405 |
Intel Celeron G1820 2.7 Ghz 2M tray |
53 |
0F11000 |
3.5-inch 25.4 mm 2 TB 32 MB 7200 RPM |
9.1 |
KVR16E11S8 |
4 GB 1600 Mhz DIMM SR x8 with TS Kingston F |
4.05 |
112.55 Watts total |
VA is 140.69, with a 0.8 power factor.
Minimum requirements for installing the SVP software on customer-supplied server hardware
Hitachi Vantara allows the SVP software to be installed on customer-supplied servers that meet the following minimum requirements.
- Processor:
- One core with hyper-threading, two cores without hyper-threading
- Processor performance comparable to Celeron 1.6 GHz
- Random-access memory: 3.5 GB per storage system
- Hard drive : 120 GB per storage system
- LAN connection: one 1000Base-T
- Operating system:
- Windows 7 Professional x64 Service Pack 1 (64 bit)
- Windows 10 Professional (64 bit)
- Windows 10 Enterprise (64 bit)
- Windows Server 2012 (64 bit)
- Windows Server 2012 R2 (64 bit)
Virtual SVP requirements
The virtual SVP must meet the following minimum requirements.
ESX Server (provided by the customer)
- VMware ESXi server 6.x
- Two quad core processors, Intel Xeon 2.29 GHz
- One port network interface card (NIC)
- SVP guest OS
- 32 GB RAM
SVP Guest OS (maximum one DKC per SVP guest OS)
- Two virtual CPUs
- One virtual network adapter
- 4 GB RAM
- 120 GB disk space
- One of the following operating systems:
- Windows 7 Professional x64 Service Pack 1 (64-bit)
- Windows 10 Professional (64-bit)
- Windows 10 Enterprise (64-bit)
- Windows Server 2012 (64-bit)
- Windows Server 2012 R2 (64-bit)
Miscellaneous
- WinZip
Minimum requirements for a Linux KVM SVP
An SVP that will be used in a Linux KVM environment requires the following minimum requirements.
Prerequisites
Linux KVM Server (provided by the customer)
- Oracle Linux 7.x server
- Two quad core processors, Intel Xeon 2.29 GHz
- One-port NIC
- SVP guest OS
- 128-GB RAM
SVP Guest OS (1 DKC) (maximum 1 DKC per SVP guest OS)
- Two vCPUs
- One virtual network adapter
- 4-GB RAM
- 120-GB disk space
- One of the following operating systems:
- Windows 7 Professional x64 Service Pack 1 (64 bit)
- Windows 10 Professional (64 bit)
- Windows 10 Enterprise (64 bit)
- Windows Server 2012 (64 bit)
- Windows Server 2012 R2 (64 bit)
Miscellaneous
- WinZip
Minimum requirements for Hyper-V Server 2012 R2 VM
A host that runs the SVP software on a customer-supplied Microsoft Hyper-V Server 2012 R2 VM requires the following minimum requirements.
- Hyper-V Server Windows 2012R supplied by the customer
-
Two quad core processors, Intel Xeon 2.29 GHz
- One-port NIC
- SVP guest OS
- 32-GB RAM
The SVP guest (1 DKC) (maximum one DKC per SVP guest OS)
- Two vCPUs
- One virtual network adapter
- 4-GB RAM
- 120-GB disk space
- One of the following operating systems:
- Windows 10 Professional (64 bit)
- Windows 10 Enterprise (64 bit)
- Windows Server 2008 R2 (64 bit)
- Windows Server 2012 (64 bit)
- Windows Server 2012 R2 (64 bit)
To use Hyper-V Manager successfully, you must first configure your hosts correctly. In particular, confirm that each host:
- Is licensed for Windows 2012R2 OS.
- Meets the shared storage requirements for Hyper-V Management.
- Meets the networking requirements for Hyper-V Management.