Electrical specifications
The VSP G1000, VSP G1500, and VSP F1500 storage system PDUs support both single-phase or three-phase AC power. The system components use single phase 220 VAC.
Item |
Input Power to PDUs |
Input Current1 |
Steady Current2 |
Leakage Current |
Inrush Current | ||
1st (0-p) |
2nd (0-p) |
1st (0-p) Time (-25%) | |||||
DKC PS |
Single phase, 2 pole + ground AC 200 V -8% min to AC 240 V +6% max3 |
7.18A |
3.59A |
0.28mA |
20A |
15A |
80ms |
UBX PS |
2.07A |
1.04A |
1.75mA |
25A |
20A |
150ms | |
SBX PS |
2.61A |
1.31A |
1.75mA |
25A |
20A |
150ms | |
FBX PS |
2.83A |
1.42A |
2.8mA |
20A |
10A |
80ms | |
Notes:
|
Power Supply Locations
The following figure shows the locations of the power supplies in a controller chassis, LFF/SFF drive chassis, and FMD chassis.
Phase |
Location |
PDU Plug |
Operating / Max Voltage Rating |
Max Current Rating |
No. of CB per PDU |
Breaker Rating | |
Single2 |
Americas PDU-121112F10 |
NEMA L6 30P twistlock 2 pole, 3 wire A + B + gnd |
208 VAC |
30A |
2 UL489 |
16A, 20 A trip | |
EMEA, APAC A3CR-123294-51 |
IEC 309, blue 2 pole, 3 wire A + B + gnd |
230 VAC / 250 VAC |
32A |
2 UL489 |
16A, 20 A trip | ||
Three3 |
Americas PDU-32C13800F10 |
NEMA L15 30P 3 pole, 4 wire A + B + C + gnd |
208 VAC / 240 VAC |
30A per phase |
3 UL489 |
15A 2 pole | |
EMEA, APAC A3CK-243694-50 |
IEC 309, red 4 pole, 5 wire A + B + C + Neut + gnd |
400 VAC |
32A per phase |
3 UL489 |
16A 2 pole | ||
Notes: 1The numbers in this table were provided by the PDU manufacturer’s specifications. For information about the PDUs, see Power distribution units for Hitachi Universal V2 Rack. 2Americas: Single phase, 30 Amp PDU, (12) IEC C13. EMEA/APAC: Single phase, 32 Amp PDU, (12) IEC C13; (2) IEC C19 . 3Americas: Method three phase, 30 Amp PDU, (24) IEC C13; (6) IEC C19. EMEA/APAC: Minkels three phase, 32 Amp PDU, (24) IEC C13; (6) IEC C19. |