Specifications

The Hitachi Virtual Storage Platform E990 (VSP E990) storage system is designed to operate in a controlled environment such as a data center. The following tables provide the environmental, electrical, and physical requirements and specifications for the VSP E990.

Environmental specifications

The following tables provide the environmental specifications, including operating and non-operating, for the VSP E990 storage system.

Table 1: Temperature
State Specification
Operating 10°C to 35°C (50°F to 95°F)
Non-operating -10°C to 50°C (14°F to 122°F)
Transport, storage -30°C to 60°C (-22°F to 140°F)
Temperature change rate 10°C/hr (18°F/hr)
Table 2: Humidity
State Specification
Operating 8% to 80%
Non-operating 8% to 90%
Transport, storage8% to 90%
Maximum wet bulb temperature (°C) 29°C (84.2°F) (noncondensing)
Table 3: Vibration, shock, and impact
TypeStateSpecifications
VibrationOperating0.98 m/s2 (0.1 G) or less [frequency component 5 Hz to 100 Hz]
Non-operatingSame as operating specification
Impact OperatingNo impact
Non-operating78.4 m/s2 (8.0 G), 15 ms
Seismic wave Operating2.5 m/s2 (0.25 G) (approximately 250 Gal) or less
Non-operating

3.9 m/s2 (0.4 G) or less: No critical damage for product function (normal operating with part replacement).

9.8 m/s2 (1.0 G) or less: Ensure own safety with fall prevention.
Table 4: Altitude (Temperature range)
State Specification
Operating (m) 3,050 m (10°C to 28°C) [10,006 ft. (50°F to 82.4°F)]

950 m (10°C to 35°C) [3,116 ft. (50°F to 95°F)]

Non-operating (m) -60 m to 12,000 m (-196 ft. to 39,370 ft.)
Table 5: Environment/atmosphere
Type StateSpecifications
DustOperating0.15 µg/m3 or less
Non-operating-
Gaseous contaminantsOperatingWithin ANSI/ISA S71.04-2013 G1 classification levels.

Keep data center clean by monitoring and controlling gaseous contamination.

Non-operating
Table 6: Noise level (recommended)
State Specification
Operating 90 dB or lower*
Non-operating
* Fire suppression systems and acoustic noise: When activated, some inert-gas fire-suppression systems release pressurized gas at high velocity through multiple nozzles in the data center, generating high levels of acoustic noise. Pneumatic sirens can also generate high levels of acoustic noise. High levels of acoustic noise can cause vibrations to the hard disk drives (HDDs) in the storage system, resulting in I/O errors, performance degradation in the drives, and to some extent damage to the drives. HDD noise-level tolerance varies among different models, designs, capacities, and manufacturers.

The recommended acoustic noise level of 90 dB or less represents the current operating environment guidelines for which the storage systems are designed and manufactured for reliable operation when placed 2 meters or more from the source of the noise.

NoteThe storage systems and HDDs are not tested for compatibility with fire-suppression systems or pneumatic sirens. In addition, Hitachi does not recommend or claim compatibility with any fire-suppression systems or pneumatic sirens. The customer is responsible for following applicable regulations.

To prevent I/O errors and damage to the storage system due to high levels of acoustic noise:

  • Install noise-reducing baffles to mitigate the noise to the HDDs in the storage system.
  • Consult the fire-suppression-system manufacturer about noise-reduction nozzles to protect the HDDs in the storage system.
  • Locate the storage system as far away as possible from noise sources.
  • If it can be done safely and without risk of personal injury, shut down the storage system before the noise occurs to prevent data loss due to damage to the HDDs in the storage system.

DAMAGE TO HARD DISK DRIVES FROM FIRE-SUPPRESSION SYSTEMS OR PNEUMATIC SIRENS VOIDS THE HARD DISK DRIVE WARRANTY.

Electrical specifications

The VSP E990 runs on single-phase AC power. The AC power input for the VSP E990 storage system has a duplex PDU architecture that enables the equipment installed in the rack to remain powered on if power is removed from one of the two power distribution panels.

The following tables provide the electrical specifications for the VSP E990 storage system, including input power and input voltage and frequency requirements.

Table 1: Input power specifications
Item Component Specification
Rated powerController1,600 VA
Drive tray800 VA
Input power1ControllerSingle-phase AC

50 Hz/60 Hz

200 V to 240 V

Drive tray
Input current1,2Controller8.0 A
Drive tray4.0 A
Steady current3Controller4.0 A
Drive tray2.0 A
Leakage currentController1.75 mA
Drive tray
Inrush currentController1st (0-p): 30 A

2nd (0-p): 20 A

1st (0-p) time: 25 ms

Drive tray1st (0-p): 30 A

2nd (0-p): 25 A

1st (0-p) time: 25 ms

Power cord plug typeControllerIEC60320 C14GUID-DE4AA3A1-D767-43E0-A9DE-A2815E3754F7-low.png
Drive tray
Notes:
  1. When planning the air-conditioning equipment and power-supply system, use the multiplied value of [Input Power] × [Input Current].
  2. The maximum current of AC input is not a redundant configuration.
  3. The maximum current of AC input is a redundant configuration.
Table 2: Input voltage and input frequency requirements
FrequencyInput Voltage (AC)ConditionsTolerance (%)
60 Hz ±2 Hz200 V to 240 V1 phase

2 wire + ground

+10% or -11%
50 Hz ±3 Hz200 V to 240 V1 phase

2 wire + ground

+10% or -11%
60 Hz ±2 Hz100 V to 120 V1 phase

2 wire + ground

+10% or -11%
50 Hz ±3 Hz100 V to 120 V1 phase

2 wire + ground

+10% or -11%

Physical specifications

The following table provides the physical specifications for the VSP E990 storage system, including weight, heat output, power consumption, and air flow specifications.

Table 1: Weight, heat output, power consumption, and air flow specifications
Model numberWeight (kg)2Heat output (W)2Power consumption (VA)1,2Air flow (m3/min)3
DW850-CBL55.24534936.0
DW850-CBLA54.24534936.0
DW-F850-CBLFB2----
DW-F850-DBN14.92903054.1
DW-F850-DBNFB20.6---
DW-F800-NMC1F0.15---
DKC-F910I-BN8G0.516.217.1-
DW-F850-CM16G0.02244.2-
DW-F850-CM32G0.05444.2-
DW-F850-CM64G0.0544.85.0-
DW-F850-CM64GL0.0544.85.0-
DW-F850-BM550.255.2
DW-F850-BM5E0.255.2
DW-F850-BM650.26.56.8
DW-F850-BM6E0.26.56.8
DW-F800-BAT0.624.425.7
DW-F800-4HF32R0.517.919.9
DW-F800-2HS10S0.518.018.9
DW-F800-2HS10B0.528.530.0
DKC-F810I-1PL160.020.790.88
DKC-F810I-1PS160.020.941.05-
DKC-F810I-1PS320.021.291.43-
DW-F800-CHBB33.22222302.0
DW-F850-CBSFB20.5---
DKC-F910I-1R9RVM0.2125.026.0-
DKC-F910I-3R8RVM0.2125.026.0-
DKC-F910I-7R6RVM0.2125.026.0-
DKC-F910I-15RRVM0.2125.026.0-
  1. Actual values at a typical I/O condition. (Random Read and Write, 50 IOPSs for HDD, 2500 IOPSs for SSD, Data Length: 8k bytes. All fans rotate at normal.) These values may increase for future compatible drives.
  2. The value is from the configuration of Model List.
  3. The value is MAX level.