Specifications
The Hitachi Virtual Storage Platform storage system use the following specifications.
Storage system specifications
The following table lists the technical specifications of the Hitachi Virtual Storage Platform 5000 series storage system.
Item |
Specification | |||
System |
Number of 2.5-inch drives |
Maximum |
768 | |
Number of 3.5-inch drives |
Maximum |
384 | ||
Number of FMDs |
Maximum |
192 | ||
Number of NVMe* | Maximum | 96 | ||
RAID group configuration | RAID 6 |
| ||
RAID 5 |
| |||
RAID 1 |
| |||
Maximum number of spare drives |
64 spare or data disks | |||
Maximum number of volumes |
65,280 | |||
Maximum storage system capacity (physical capacity) |
30 TB 2.5-inch SSD used |
20.5 PiB | ||
7.6 TB 2.5-inch NVMe SSD* | 0.64 PiB | |||
Maximum external configuration |
255 PiB | |||
Memory |
Cache memory capacity |
VSP 5100H:
VSP 5500H:
| ||
Storage interface |
DKC-DB interface |
SAS/Dual Port NVMe/Dual Port* | ||
Data transfer rate | SAS Interface |
12 Gbps | ||
NVMe (PCIe) Interface* | 8 Gbps | |||
Number of DKB |
VSP 5100H: 4 VSP 5500H: 8 | |||
Device interface |
Support channel type |
Open System |
NoteBy replacing
SFP transceiver of the fibre port on the Channel Board to SFP
for Longwave, the port can be used for the Longwave.
| |
Mainframe |
Fibre Channel Short Wave/Fibre Channel Long Wave | |||
Data transfer rate |
Fibre Channel |
Open System : 4/8/16/32 Gbps Mainframe : 4/8/16 Gbps | ||
iSCSI (Optic) |
10 Gbps | |||
Maximum number of CHB |
VSP 5100H: 8 VSP 5500H: 16 | |||
Note
*NVMe drives are only available on VSP 5500H storage systems. |
Item |
Specification | |||
System |
Number of 2.5-inch drives |
Maximum |
1,536 | |
Number of 3.5-inch drives |
Maximum |
768 | ||
Number of FMDs |
Maximum |
384 | ||
RAID group configuration | RAID 6 |
| ||
RAID 5 |
| |||
RAID 1 |
| |||
Maximum number of spare drives |
128 spare or data disks | |||
Maximum number of volumes |
65,280 | |||
Maximum storage system capacity (physical capacity) |
30 TB 2.5-inch SSD used |
41.0PiB | ||
Maximum external configuration |
255 PiB | |||
Memory |
Cache memory capacity |
4 TB | ||
Storage interface |
DKC-DB interface |
SAS/Dual Port | ||
Data transfer rate |
12 Gbps | |||
Number of DKB |
16/8 | |||
Device interface |
Support channel type |
Open System |
NoteBy replacing SFP transceiver of the fibre
port on the Channel Board to SFP for Longwave, the port can be
used for the Longwave.
| |
Mainframe |
Fibre Channel Short Wave/Fibre Channel Long Wave | |||
Data transfer rate |
Fibre Channel |
Open System : 4/8/16/32 Gbps Mainframe : 4/8/16 Gbps | ||
iSCSI (Optic) |
10 Gbps | |||
Maximum number of CHB |
32 |
Item |
Specification | |||
System |
Number of 2.5-inch drives |
Maximum |
2,304 | |
Number of 3.5-inch drives |
Maximum |
1,152 | ||
Number of FMDs |
Maximum |
576 | ||
RAID group configuration | RAID 6 |
| ||
RAID 5 |
| |||
RAID 1 |
| |||
Maximum number of spare drives |
192 spare or data disks | |||
Maximum number of volumes |
65,280 | |||
Maximum storage system capacity (physical capacity) |
30 TB 2.5-inch SSD used |
61.5PiB | ||
Maximum external configuration |
255 PiB | |||
Memory |
Cache memory capacity |
6 TB | ||
Storage interface |
DKC-DB interface |
SAS/Dual Port | ||
Data transfer rate |
12 Gbps | |||
Number of DKB |
24/16/8 | |||
Device interface |
Support channel type |
Open System |
NoteBy replacing SFP transceiver of the fibre
port on the Channel Board to SFP for Longwave, the port can be
used for the Longwave.
| |
Mainframe |
Fibre Channel Short Wave/Fibre Channel Long Wave | |||
Data transfer rate |
Fibre Channel |
Open System : 4/8/16/32 Gbps Mainframe : 4/8/16 Gbps | ||
iSCSI (Optic) |
10 Gbps | |||
Maximum number of CHB |
48 |
Mechanical environmental specifications
The following tables list the mechanical environmental conditions for the Hitachi Virtual Storage Platform 5000 series storage systems.
Item |
In operation |
In non-operation | |
Vibration value of storage system |
0.25Grms, 5-500Hz, 30min. |
0.6Grms, 3-500Hz, 30min. | |
Vibration value of chassis |
- |
|
Electrical specifications
The Hitachi Virtual Storage Platform 5000 series storage system Power Distribution Units (PDUs) support single-phase AC power.
The Hitachi rack comes with either two or four PDUs, depending on the PDU model selected. The PDUs are installed vertically in the rack.
- If two PDUs are selected, one will be installed on the left side of the rack and the other will be installed on the right side.
- If four PDUs are selected, the PDUs will be half-length and mounted vertically, one above the other, with two on the left side of the rack and two on the right side.
If you need assistance using this tool, contact Hitachi Vantara Support at https://support.hds.com/en_us/contact-us.html.
Item | Input Power | Inrush Current (Rating) 1 | Leakage Current | Inrush Current | |||
When one PS is operating | When two PSs are operating | 1st (0-p) | 2nd (0-p) | 1st (0-p) Time (-25%) | |||
Node power supply | Single phase, AC200V to AC240V | 7.2 A | 3.6 A | 1.75 mA | 30 A | 30 A | 25 ms |
DBPS (DBS2) | 3.2 A | 1.6 A | 1.75 mA | 30 A | 30 A | 25 ms | |
DBPS (DBL) | 2.0 A | 1.0 A | 1.75 mA | 30 A | 30 A | 25 ms | |
DBPS (DBF3) | 3.1 A | 1.55 A | 1.75 mA | 20 A | 15 A | 80 ms | |
DBPS (DBN) | 4.0 A | 2.0 A | 1.75 mA | 30 A | 30 A | 25 ms | |
Node interconnect switch power supply | 1.2 A | 0.6 A | 1.75 mA | 30 A | 30 A | 25 ms | |
|
The following table shows the supported input voltage and frequency for the controller chassis, drive box, and node interconnect switch.
Input voltage | Voltage tolerance | Frequency | Wire connection |
200V to 240V | +10% or -11% |
50Hz ± 2Hz 60Hz ± 2Hz | 1 Phase 2 Wire + Ground |
|
Environmental specifications
The following table lists the environmental specifications for the Hitachi Virtual Storage Platform 5000 series storage systems.
Item |
Condition | ||
Operating |
Not operating |
Shipping and storage | |
Temperature range |
10 ºC to 40 ºC6 |
-10 ºC to 50 ºC |
-30 ºC to 6 0ºC |
Relative Humidity (No dew condensation) |
8% to 80% |
8% to 90% |
5% to 95% |
Max. Wet Bulb |
29 ºC |
29 ºC |
29 ºC |
Temperature gradient per hour |
10 ºC |
10 ºC |
10 ºC |
Dust |
0.15 or less |
- |
- |
Gaseous contaminants2 |
G1 classification levels | ||
Altitude (m) |
3 ~ 3,050 (10 ºC ~ 28 ºC) ~ 950 (10 ºC ~ 40 ºC)6 |
-60 to 3,000 |
-60 to 3,000 |
Noise Level (Recommended) |
90 dB or less1 |
- |
- |
Chassis Acoustic Level 45 |
|
|
- |
|
Component power consumption, heat output, and airflow
The following table provides power consumption, heat output, and airflow specifications of the individual Virtual Storage Platform 5000 series system components.
Component |
Component model number |
Power consumption (VA) |
Heat output |
Airflow (m3/min) |
Weight (lb/kg) |
Primary controller chassis | DKC910I-CBX | 756 | 718 | 5.4 | 70.0 |
Secondary controller chassis | DKC-F910I-CBX2 | 491 | 466 | 3.0 | 41.6 |
SFF drive chassis |
DKC-F910I-SBX |
1,221 |
1,160 |
12.8 |
68 |
LFF drive chassis |
DKC-F910I-UBX |
674 |
640 |
18.9 |
126.0 |
FMD Drive Chassis |
DKC-F910I-FBX |
473 |
450 |
6.4 |
76.7 |
Controller Chassis Bezel |
DKC-F910I-CBLFB |
- |
- |
- |
1.0 |
Controller Chassis Bezel |
DKC-F910I-CBLFBA |
- |
- |
- |
1.2 |
Drive Chassis Bezel |
DKC-F910I-DBFB |
- |
- |
- |
0.5 |
Drive Chassis Bezel |
DKC-F910I-DBFBA |
- |
- |
- |
0.5 |
HSN Chassis Bezel |
DKC-F910I-HSNFB |
- |
- |
- |
0.6 |
HSN Chassis Bezel |
DKC-F910I-HSNFBA |
- |
- |
- |
0.6 |
Flash Module Bezel |
DKC-F910I-FBFB |
- |
- |
- |
0.7 |
Flash Module Bezel |
DKC-F910I-FBFBA |
- |
- |
- |
0.9 |
Additional Service Processor |
DKC-F910I-SVP |
16.0 |
16.0 |
- |
0.7 |
Additional RAID Controller Kit | DKC-F910I-CTL | 491 | 466 |
- | 11.4 |
Safety Cover for empty CTL slot | DKC-F910I-SCFC |
- |
- |
- | 1.8 |
Additional Hub |
DKC-F910I-HUB |
12.0 |
12.0 |
- |
0.5 |
Fan Module |
DKC-F910I-FANM |
22.7 |
21.6 |
- |
1.1 |
Operation Panel Kit |
DKC-F910I-OPPNL |
1.0 |
1.0 |
- |
0.37 |
Mainframe Fibre 4-port 16G Host Adapter for Shortwave |
DKC-F910I-4MS16 |
19.3 |
18.3 |
- |
0.5 |
Mainframe Fibre 4-port 16G Host Adapter for Longwave |
DKC-F910I-4ML16 |
19.3 |
18.3 |
- |
0.5 |
Fibre 4-port 32Gbps Ready Host Adapter |
DKC-F910I-4HF32R |
24.9 |
22.4 |
- |
0.5 |
iSCSi 2-port 10G Host Adapter |
DKC-F910I-2HS10S |
18.9 |
18.0 |
- |
0.5 |
SFP for 16Gbps Longwave |
DKC-F810I-1PL16 |
- |
- |
- |
0.02 |
SFP for 16Gbps Shortwave |
DKC-F810I-1PS16 |
- |
- |
- |
0.02 |
SFP for 32Gbps Shortwave |
DKC-F810I-1PS32 |
- |
- |
- |
0.02 |
Disk Adapter |
DKC-F910I-BS12G |
17.2 |
16.0 |
- |
0.5 |
Encryption Disk Adapter |
DKC-F910I-BS12GE |
17.2 |
16.0 |
- |
0.5 |
Cache Memory 64GB | DW-F850-CM64GL | 5.0 | 4.8 | - |
0.054 |
Cache Flash Memory 45 |
DKC-F910I-BM45 |
6.8 |
6.5 |
- |
0.2 |
Cache Flash Memory 45 with encryption |
DKC-F910I-BM4E |
6.8 |
6.5 |
- |
0.2 |
Rack Rail |
A34V-600-850-UNI-S.P |
- |
- |
- |
- |
HSN Chassis Rail |
3292455-001 |
- |
- |
- |
- |
Rack Rail |
A34V-600-850-UNI-S.P |
- |
- |
- |
- |
Drive Chassis Rail for FBX |
A3BF-HK-GL-740-1-S.P L |
- |
- |
- |
- |
PCIe Cable set for primary module CBXA |
DKC-F910I-MCC1 |
- |
- |
- |
0.1 |
PCIe Cable set for primary module CBXB |
DKC-F910I-MCC2 |
- |
- |
- |
0.1 |
PCIe Cable 5m |
DKC-F910I-MFC5 |
- |
- |
- |
0.2 |
PCIe Optical Module |
DKC-F910I-PQSFP |
- |
- |
- |
0.005 |
SAS Optical Module |
DKC-F910I-SQSFP |
- |
- |
- |
0.005 |
Optical Cable 10m |
DKC-F910I-MPC10 |
- |
- |
- |
0.2 |
Optical Cable 20m |
DKC-F910I-MPC20 |
- |
- |
- |
0.3 |
Optical Cable 30m |
DKC-F910I-MPC30 |
- |
- |
- |
0.4 |
Optical Cable 100m |
DKC-F910I-MPC1H |
- |
- |
- |
1.0 |
SAS Cable set for Disk Adapter |
DKC-F910I-SCCS |
- |
- |
- |
1.4 |
QSFP Metal Cable 1m |
DW-F800-SCQ1 |
- |
- |
- |
0.2 |
QSFP Metal Cable 1.5m |
DW-F800-SCQ1F |
- |
- |
- |
0.2 |
RJ45 bundled LAN Cable Kit |
DKC-F910I-LC |
- |
- |
- |
0.2 |
RJ45 Cable 5m |
DKC-F910I-LC5 |
- |
- |
- |
0.3 |
RJ45 Cable 10m |
DKC-F910I-LC10 |
- |
- |
- |
0.5 |
RJ45 Cable 20m |
DKC-F910I-LC20 |
- |
- |
- |
0.9 |
RJ45 Cable 30m |
DKC-F910I-LC30 |
- |
- |
- |
1.4 |
RJ45 Cable 100m |
DKC-F910I-LC1J |
- |
- |
- |
4.7 |
SFF 2.4TB Disk Drive |
DKC-F810I-2R4JGM |
9.4 |
9.0 |
- |
0.26 |
LFF 10TB Disk Drive |
DKC-F810I-10RH9M |
13.5 |
12.9 |
- |
0.86 |
LFF 14TB Disk Drive |
DKC-F810I-14RH9M |
13.5 |
12.9 |
- |
0.86 |
SFF 960GB SSD Drive |
DKC-F810I-960MGM |
7.0 |
6.7 |
- |
0.21 |
SFF 3.8TB SSD Drive |
DKC-F810I-3R8MGM |
7.0 |
6.7 |
- |
0.21 |
SFF 7.6TB SSD Drive |
DKC-F810I-7R6MGM |
8.3 |
7.9 |
- |
0.21 |
SFF 15TB SSD Drive |
DKC-F810I-15RMGM |
8.3 |
7.9 |
- |
0.21 |
SFF 30TB SSD Drive | DKC-F810I-30RMGM |
8.3 |
7.9 |
- |
0.21 |
7TB Flash Module Drive |
DKC-F810I-7R0FP |
26.0 |
25.0 |
- |
1.4 |
14TB Flash Module Drive |
DKC-F810I-14RFP |
26.0 |
25.0 |
- |
1.4 |
NVMe Disk Adapter |
DKC-F910I-BN8G |
17.1 |
16.2 |
- |
0.5 |
NVMe SFF Drive Chassis |
DKC-F910I-NBX |
445 |
446 |
16.4 |
15.5 |
NVMe Chassis Rail |
A3BF-HK-GL-740-1-S.P |
- |
- |
- |
- |
NVMe Cable set for NVMe Disk Adapter |
DKC-F910I-NCCS |
- |
- |
- |
1.1 |
SFF 1.9TB NVMe Drive |
DKC-F910I-1R9RVM |
26.0 |
25.0 |
- |
0.28 |
SFF 3.8TB NVMe Drive |
DKC-F910I-3R8RVM |
26.0 |
25.0 |
- |
0.28 |
SFF 7.6TB NVMe Drive |
DKC-F910I-7R6RVM |
26.0 |
25.0 |
- |
0.28 |
|